Herunterladen Inhalt Inhalt Diese Seite drucken

Taping The Tubes; Finishing The Installation; How To Install The Timer Remote Controller Or High-Spec Wired Remote Controller (Optional Part); Note - Panasonic S-15MM1E5A Installationsanleitung

Vorschau ausblenden Andere Handbücher für S-15MM1E5A:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 69

5-4. Taping the Tubes

(1) At this time, the refrigerant tubes (and electrical wiring
if local codes permit) should be taped together with
armoring tape in 1 bundle. To prevent condensation from
overflowing the drain pan, keep the drain hose separate
from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you
wrap the tubing, overlap half of each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1 clamp approx.
each meter. (Fig. 5-9)

NOTE

Do not wind the armoring tape too tightly since this will
decrease the heat insulation effect. Also ensure that the
condensation drain hose splits away from the bundle and drips
clear of the unit and the tubing.

5-5. Finishing the Installation

After finishing insulating and taping over the tubing, use sealing
putty to seal off the hole in the wall to prevent rain and draft from
entering. (Fig. 5-10)
6. HOW TO INSTALL THE TIMER REMOTE CONTROLLER OR HIGH-SPEC WIRED
REMOTE CONTROLLER (OPTIONAL PART)
NOTE
Refer to the Operating Instructions attached to the optional Timer Remote Controller or optional High-spec Wired Remote Controller.

7. HOW TO INSTALL WIRELESS REMOTE CONTROLLER RECEIVER

NOTE
Refer to the Operating Instructions attached to the optional Wireless Remote Controller Receiver.
Apply putty here
18
Clamp
Drain hose
Insulated tubes
Fig. 5-9
Tubing
Fig. 5-10

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis