Control Box Reset; Recycle Function; Logging Of Burner Operating Parameters - Riello MO550 Handbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

LED COLOUR CODE OF THE CONTROL BOX RESET BUTTON
Operation status
Wait
Preheating
Pre-purging
Long pre-purging
Transformer turn on
Flame regular
Post-purging
Recycle
Continuous purging (*)
Extraneous light during preheating or wait
Extraneous light during post or continuous purging (*)
Extraneous light in block
Block
Block with continuous purging (*)
(*) only for applications provided for.
BLOCK TYPES AND INTERVENTION TIMES IF THE BURNER FAILS
DESCRIPTION OF THE FAILURE TYPES
Oil heater failure: the start up thermostat (K) does not make the switch
Extraneous light when the burner is turned on and off
Presence of extraneous light during the oil pre-heating
Presence of extraneous light in pre-purging
Extraneous light presence during the post-purging or continuous purging (*)
Disappearance of the flame during operation
The flame is not detected after the safety time
(*) only for applications provided for.

CONTROL BOX RESET

To reset the control box, proceed as follows:
Press and hold the reset button for between 1 and 2 seconds. If the burner does not restart, you must
®
make sure the limit thermostat ( TL ) is closed.
If the control box reset button continues to blink signalling the cause of the failure (RED LED), it is
®
necessary to press the button again for no more than two seconds.

RECYCLE FUNCTION

The control box allows a recycle, i.e. complete repetition of the start-up programme, making up to
3 attempts, in the event the flame goes out during operation.
If the flame goes out again, this will cause the burner to lock out. If there is a new demand for heat during
the recycle, the 3 attempts are reset when the limit thermostat ( TL ) switches.

LOGGING OF BURNER OPERATING PARAMETERS

With this control box, data - i.e. the number of blocks that have occurred, the type of block that has occurred
(just the last one) and the oil valve opening operating time - can be logged even when there is no power supply.
That way, you can determine how much fuel has been consumed during operation.
Do the following to display the diagnostic:
Connect the kit supplied separately to the appropriate socket on the control box.
®
The information is read after the software program in the kit is booted.
3232
LED colour codes
LED off
Yellow
Green
Green
Green + Yellow blinking
Green + Yellow blinking
Green + Yellow
Green + Yellow blinking
Green
Yellow blinking
Green + Yellow blinking
Red + Yellow blinking
Red
Red + Green
6
GB
ON
OFF
Blinking
speed
Seconds
Fast
0.3
0.3
Slow
0.3
2
Medium
2
1
Fast
0.3
0.3
Fast
0,3
0,3
Fast
0,3
0,3
BLOCK
After max. 6 minutes
After max. 30 seconds
After max. 30 seconds
Within 1 second
After max. 30 seconds
After 3 recycles
Immediate