Herunterladen Inhalt Inhalt Diese Seite drucken

Control Box Visual Diagnostics - Riello MO550 Handbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

®
Connect the connection of the 2nd
stage coil (1, fig. 8), already present
in the burner using the connection
assembly (2) supplied, observing
the following procedure.
- Cut both the cables (3 - 4), and
use the jacks (5) to join the wires
of the second stage coil to the
4 pin socket connection (2).
- Connect the connector (6) to posi-
tion ( V2 , fig. 2 page 1) of the con-
trol box.
In conclusion, make the rest of the
®
connections to the control box.

CONTROL BOX VISUAL DIAGNOSTICS

The control box features a diagnostics function through which any causes of malfunctioning can be identi-
fied (indicator: RED LED ).
To use this function, you must press and hold the reset button for at least 3 seconds once it has entered the
safety condition ( lockout ).
The control box generates a sequence of led pulses, which is repeated at constant 2-second intervals.
RED LED illuminated
press and hold reset for 3 sec.
The sequence of led pulses issued by the control box identifies the possible types of malfunction, which are
listed in the table below.
SIGNAL
2 led pulses
4 led pulses
7 led pulses
8 led pulses
To reset the control box after visual diagnostics have been displayed, you must press
WARNING
the reset button.
3232
Fig. 8
6
2
The flame does not stabilise at the end of the safety time:
√ flame detector defective or dirty;
√ oil valve defective or dirty;
√ faulty ignition transformer;
√ badly regulated burner.
Light present in the chamber before the burner»s switching on or off:
√ presence of a strange light before or after the limit thermostat switching over;
√ presence of a strange light during pre-purging;
√ presence of a strange light during post-purging.
Loss of flame during operation:
√ badly regulated burner;
√ oil valve defective or dirty;
√ flame detector defective or dirty;
Check and control of the oil heater (if there is one):
√ faulty control thermostat or heater.
Interval
Led pulses
PROBABLE CAUSE
3
GB
5
3
1
2s
Led pulses
4

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading