EN
A
MOUNTING
[1] Choose the optimal location: flat and large surface
[2] Mount the KNX 4 DC Motor Controller WM
[3] Use cable tie!
[4] Keep to minimum distance
B
CABLING
[1] Tool for all terminals
[2] Wiring diagram
[3] Check the correct running direction of the end product
UP: the end product goes up ( C + )
STOP: the end product stops ( C + + )
DOWN: the end product goes down ( C + )
m To close window press UP, to open window press DOWN.
[4] Possible switches
1.
Smoove Origin IB, Ref. 1811272
2.
Double push button
CHARACTERISTICS
Supply voltage
Power Supply
Stand-by current / Stand-by power (IEC 62301)
Supply voltage from KNX bus
Rated current consumption KNX
Max. motor current consumption
Supply voltage of group control input
Supply voltage of local push buttons
Terminals
Relay micro-gap
Terminal KNX
Running time per output
Operating temperature
Relative humidity
Material of housing
Housing dimensions (w x h x d)
Weight
Degree of protection
Protection class
Pollution degree
Conformity
CABLE
Connection to ... Cable
Motors
Min.: 2 x 0.6 mm/22 AWG / Max.: 2 x 2.5 mm
Switch
Min.: 3 x 0.6 mm/22 AWG / Max.: 3 x 2.5 mm
Group control
Min.: 3 x 0.6 mm/22 AWG / Max.: 3 x 1.5 mm
KNX bus
2 x 0.8 mm/20 AWG
24 V DC
Min.: 2 x 1.5 mm
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an approved collection point for recycling.
m Control of non Somfy motors only on request and after approval by Somfy
24 V DC (min. 21.5 V - max. 28 V DC)
Regulated and short circuit proof power supply, certified and suitable for the connected motors
25 mA@24 V DC / 600 mW@24 V DC
KNX voltage 21 ... 30 V DC, SELV
As per KNX guidelines, 10 mA
4 x 2.5 A@24 V DC
SELV, 16 V DC
SELV, 16 V DC
Spring connectors
μ
KNX bus terminal (black/red)
Max. 5 minutes
- 5 ° C ... + 45 ° C
Max. 85 %
PC-ABS
180 x 255 x 61 mm
710 g
IP 20
2
www.somfy.com/ce
/13 AWG –
2
/13 AWG Recommended
2
/15 AWG Recommended
2
/15 AWG / Max.: 2 x 2.5 mm
/13 AWG –
2
2
C
COMMISSIONING AND OPERATING
[1] Reset/Prog button
Is the access to the basic configuration of the Motor Controller.
[2] Selection of the push button ergonomic
Local push button ergonomics and the type of end products to be preselected:
• Screen mode (SCR)
• Venetian blind, European mode
• Venetian blind, US mode (default mode)
1.
To toggle between modes, press shortly the Reset / Prog button. Repeat
until the LED, according to the desired configuration, lights up.
2.
Save and exit
[3] Factory RESET
[4] Learn running time/length
1.
Drive screen to upper end limit
2.
Press Stop until screen drives down on its own
3.
Press shortly Stop when lower end limit is reached
[5] Learn and recall intermediate position (IP)
1.
Recording
2.
Recalling
Twisted pair
Required, following KNX topology guidelines
Max. length
Stripping length
6 mm/0.24"
100 m/330 ft
6 mm/0.24"
100 m/330 ft
6 mm/0.24"
6 mm/0.24"
10 m/33 ft
6 mm/0.24"
animeo KNX 4 DC Motor Controller WM. Ref. 5138035A -