10. Troubleshooting

Disturbance
Discharge valve opens without
apparent reason
Discharge valve don't close
Flow is too low
Honeywell GmbH
", outlet check valve in dezincifi-
2
Cause
Pressure strokes in water supply system Install a pressure reducing valve upstream the
Fluctuating inlet pressure
Cartridge insert is contaminated
Deposits on valve seat
Damaged 'o'ring
Leaky discharge valve
Inlet strainer is blocked
GB
Remedy
backflow preventer
Install a pressure reducing valve upstream the
backflow preventer
Remove cartridge insert and exchange it
Remove cartridge insert and clean or exchange it
Remove cartridge insert and exchange it
Remove cartridge insert and clean or exchange it
Remove strainer and clean it