CAUTION
Incorrect measured values with incorrect grounding
The device must not be grounded via the "+" connection. It may otherwise malfunction and be permanently damaged.
● If necessary, ground the device using the "-" connection.
Note
Electromagnetic compatibility (EMC)
You can use this device in industrial environments, households and small businesses.
For metal housings there is an increased electromagnetic compatibility compared to high-frequency radiation. This
protection can be increased by grounding the housing, see section "Connecting the device (Page 16)".
Note
Improvement of interference immunity
● Lay signal cables separate from cables with voltages > 60 V.
● Use cables with twisted wires.
● Keep device and cables in distance to strong electromagnetic fields.
● Use shielded cables to guarantee the full specification according to HART.
● Connect a load resistor of at least 230 Ω in series in the signal circuit in order to guarantee fault-free HART
communication. When power supply isolators are used for HART transmitters, e.g. SITRANS I, a load resistor is already
installed in the device.

Connecting the device

Opening the device
1. Unscrew the cover of the electrical cable compartment.
2. Unscrew the cable gland cover and remove the plastic seal.
Connecting the device
Note
The following values can be set for the load:
● 230 to 1100 Ω for the HART communicator
● 230 to 500 Ω for the HART modem
1. Strip approximately 15 cm from the outer sheath of the cable.
2. Insert the wires of the connecting cable through the cable gland and lead them through the guide channel. The guide
channel connects the cable gland to the connecting terminals.
3. If you have a plastic cable gland, connect the shield to the ground terminal
connected to the enclosure.
4. If you have a metal cable gland, ground the shield to the cable gland ground terminal
– Leave approx. 2 cm of extra shield.
16
. The ground terminal is electrically
as follows:
SITRANS P300 (7MF8.23.. 7MF8.24.. 7MF8.25..)
A5E03434657-01, 08/2011