4. Status LEDs

The module has two status LEDs, see fig. 1:
LED1: Red/green status LED for Ethernet
communication.
LED2: Red/green status LED for communication
between the module and the Grundfos product.
LED1, GRM IP
Status
Description
No GRM IP communication or
Off
switched off.
Flashing green
Startup period (120 sec.)
Permanently
Communication with GRM server
green
established.
Flashing green
Data transmitting to GRM server.
(0.3 Hz)
GRM communication lost or no
Flashing red
communication to GRM server.
Resetting to factory settings.
Flashing red
After 20 sec. the CIM 500 will
and green
restart.
LED1, Modbus TCP/BACnet IP
Status
Description
No Modbus/BACnet
Off
communication or switched off.
Modbus/BACnet communication
Flashing green
active.
Module configuration fault. See
Permanently
section
red
IP.
Error in firmware download. See
Permanently
section
red and green
IP.
Resetting to factory settings.
Flashing red
After 20 seconds the CIM 500 will
and green
restart.
8
6.1 Modbus TCP/BACnet
6.1 Modbus TCP/BACnet
LED1, PROFINET IO
Status
Description
Off
The module is switched off.
Wink function. LED will flash 10
Flashing green
times when activated from
master.
The module is ready for data
Permanently
transmission (data exchange
green
state).
Wrong or missing PROFINET IO
configuration. See section
Flashing red (3
6.2 PROFINET
Hz, duty cycle
Restart the CIM 500. Use the
50 %)
RESTART button from the web
server PROFINET configuration.
Pulsing red
Configured, but connection to
(0.3 Hz, duty
master lost. See section
cycle 10 %)
6.2 PROFINET
Permanently
Product not supported. See
red
section
Permanently
Error in firmware download. See
red and green
section
Resetting to factory settings.
Flashing red
After 20 seconds the CIM 500
and green
will restart.
LED2
Status
Description
Off
The module is switched off.
No internal communication
Flashing red
between the CIM 500 and the
Grundfos product.
Permanently
The module does not support the
red
Grundfos product connected.
Internal communication between
Permanently
the module and the Grundfos
green
product is OK.
Permanently
Memory fault.
red and green
During startup, there is a delay of up to five
Note
seconds before the status of LED1 and
LED2 is updated.