Herunterladen Inhalt Inhalt Diese Seite drucken

Grundfos CIM 500 Montage- Und Betriebsanleitung Seite 113

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 16
A.5 BACnet IP configuration
Fig. 4
Real Time Ethernet Protocol Configuration - BACnet IP
Object
Description
Select UDP Port Number. The default number is 47808 (the standard UDP port
UDP Port Number
number for BACnet IP).
Select Device Instance. The default number is 22700. The Device Instance must be
Device Instance
unique in the BACnet network. Grundfos is 227 and it is fixed. The lasts three digits
can be changed.
You can name the device. The device name must be unique in the BACnet network
Device Name
(optional).
Device Location
You can name the device location for local identification (optional).
Select the maximum Application Protocol Data Unit (between 50 and 1476).
Max APDU
The default value is 1476 bytes.
Custom device
If ticked, the CIM 500 is configured to use a BACnet custom device instance number.
instance enable
Foreign Device
If ticked, the CIM 500 is configured as a foreign device.
IP Address
Enter the foreign IP address.
UDP Port
Select the UDP port number. The default number is 47808.
Select the time period during which the foreign device must re-register on the BACnet
Re Register Time
network.
113

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis