Herunterladen Inhalt Inhalt Diese Seite drucken

Gewiss GW 10 793 Handbuch Seite 54

Eib thermostat für wandmontage
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

OPERATING INSTRUCTIONS
P12 - Speed 3 regulation differential value
When the P12 appears on the display, set the differential
regulation value to speed V3.
Possible values: from 0.2 °C to 2 °C with a pitch of 0.1
°C.
Press the
This parameter is significant if the number of fan coil stage
set by ETS is greater than 3.
NOTE 1
If the device was set as Slave with set point settings on ETS,
go to point 14; if set as Slave with mode or Stand alone
settings with remote control enabled, go to point P13. In
other cases, programming is completed. Press the SET key
to return to normal operations.
P13 - Enabling/disabling of the Slave function
When the P13 code appears on the display, it is possible to
deactivate the Slave function mode and activate the Stand
alone function mode and vice-versa (01 = Slave function
mode, 00 = Stand alone function mode).
Press the
If parameter P13=00 (Slave function disabled) go to point
P15, if P13=01 (Slave function on), go to point P14.
P14 - Set point variation interval for manual override
When P14 appears, select the admissible variation interval
(min/max) for the value to be applied to the set point for
manual override using the
symmetrical: select 3.5°C to set an interval between -3.5°C
and +3.5°C.
Possible values: from 0 °C to 5 °C, with a pitch of 0.1 °C.
The programming phase is now complete Press the SET key
to return to normal operation mode.
key within 30 seconds to confirm the value set.
key within 30 seconds to confirm the value set.
54
keys. The interval is

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis