! WARNING
• Installation and maintenance shall be performed by
qualified persons who are familiar with local code and
regulation, and experienced with this type of appliances.
• All field wiring must be installed in accordance with the
national wiring regulation.
• Ensure that the rated voltage of the unit corresponds to
that of the name plate before commencing wiring work
according to the wiring diagram.
• The unit must be GROUNDED to prevent possible
hazards due to insulation failure.
• All electrical wiring must not touch the refrigerant
piping, compressor or any moving parts of the fan
motors.
• Confirm that the unit has been switched OFF before
installing or servicing the unit.
• Disconnect from the main power supply before
servicing the air conditioner unit.
• DO NOT pull out the power cord when the power is
ON. This may cause serious electrical shocks which may
result in fire hazards.
• Troubleshooting must be performed by qualified
personnel.
• IMPORTANT: DO NOT INSTALL OR USE THE
AIR CONDITIONER UNIT IN A LAUNDRY
ROOM.
NOTICE
This product is subjected to Waste of
Electrical and Electronic Equipment
Regulations (WEEE Regulations). The
waste product shall be separately collected
by specific collection and treatment centre.
Please refer to local authority for these
centres. This is only applicable to European
Union countries.
1. Preliminary Site Survey
Obstacle
Obstacle
• Electrical supply and installation is to conform to local authority's (e.g. National Electrical Board) codes and regulations.
• Voltage supply fluctuation must not exceed ±10% of rated voltage. Electricity supply lines must be independent of welding
transformers which can cause high supply fluctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
• The indoor unit must be installed in such that is free from any obstacles in path of cool air discharge and warm air return, and
must allow spreading of air throughout the room (near the center of the room).
• Must be provide clearance for the indoor unit from the wall and obstacles as shown in the figure.
• The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying noise and
vibration.
• The installation place (hanging ceiling surface) must be assuring levelness and the height in the ceiling is 350mm or more.
• The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).

SAFETY PRECAUTIONS

Please take note of the following important points when installing.
• Do not install the unit where leakage of flammable gas may
occur.
• Ensure that drainage piping is connected properly.
• Do not overcharge the unit.
• Ensure that the unit's panel is closed after service or installation.
• Sharp edges and coil surfaces are potential locations which may
cause injury hazards.
Avoid from being in contact with these places.
• Before turning off the power supply, set the remote controller's
ON/OFF switch to the "OFF" position to prevent the nuisance
tripping of the unit. If this is not done, the unit's fans will start
turning automatically when power resumes, posing a hazard to
service personnel or the user.
• Do not operate any heating apparatus too close to the air
conditioner unit. This may cause the plastic panel to melt or deform
as a result of the excessive heat.

INSTALLATION OF THE INDOOR UNIT

Min. 0.5 m
Min. 0.5 m
Min. 0.5 m
Min. 0.5 m
Floor
Floor
3
! CAUTION
If gas leaks and accumulates around the unit, it may cause
fire ignition.
If the drainage piping is not connected properly, it may cause
water leakage.
This unit is factory pre-charged.
Overcharge will cause over-current or damage to the
compressor.
Unsecured panels will cause the unit to operate noisily.
Min. 0.5 m
Min. 0.5 m