ETS-05
ENGLISH
Installation instructions for nVent RAYCHEM ETS-05
The nVent RAYCHEM ETS-05
electronic surface and ambient
sensing thermostat provides accurate
temperature control for heating cables.
The ETS-05 is available in the following
versions:
ETS-05-L2-E
ETS-05-H2-E
ETS-05-L1-J
ETS-05-H1-J
ETS-05-L2-EP
ETS-05-H2-EP
ETS-05-A2-E
With:
L = 0°C–199°C,
H = 0°C–499°C
A= Ambient, 0°C–49°C
1 = 110V AC
2 = 230V AC
E = Europe & Asia
J = Japan
P = Earth Plate
These Thermostats are suitable for
the following applications:
Current Rating: 32A
Hazardous area:
(Zone 0)* Zone 1 and Zone 2
(*Only sensor may be located
within Zone0)
Temperature Class: T5
Gas Group IIC
Dust (Zone 21 and Zone 22)
Dust Group IIIC
2 | nVent.com
Line Sensing
Ambient Sensing
Approvals:
nVent
1180
II 2(1)G
II 2D
Ex eb ia mb [Ga] IIC T5 Gb
Ex tb IIIC T100°C Db IP66
Ta–40 to +60°C
Supply = 99-121V (110V) or
195-230V (230V)
Maximum switched current
32A Resistive
Um=253V
Baseefa13ATEX0137
IECEx BAS 13.0071
Please note: Only Ex eb and
Ex tb equipment certified
cable glands or stopping
plugs which employ a
sealing washer or gasket
may be used.
ETS-05-L2-E(P):
TC RU C-BE.ИМ43.B.01764
ООО "ТехИмпорт"
1Ex e ia mb [iaGa] IIC T5 Gb X
Ex tb IIIC T100°C Db X IP66
Ta –52°C...+60°C
ETS-05-H2-E(P):
TC RU C-BE.ИМ43.B.01764
ООО "ТехИмпорт"
1Ex e ia mb [iaGa] IIC T5 Gb
Ex tb IIIC T100°C Db IP66
Ta –60°C...+60°C
ETS-05-A2-E
No EAC Ex available yet