7.2
Warning code
Warning Code
Pv Span – Pv Zero range is below 500.
B
The angle of feedback lever is too small.
Full open/close elapsed time is less than 1
F
second.
Actuator size is too small.
Pv is below 100.
G
The angle of feedback lever is too large.
Pv is over 4000.
H
The angle of feedback lever is too large.
Description
Page 54
SR3300-8010
SR-3300
Action
Re-install the positioner.
Ensure the feedback lever does not touch the
lever stopper at 0% and 100%.
After re-installation, perform AUTO1.
Use variable orifice.
Use larger actuator.
Re-install the positioner.
Ensure the feedback lever does not touch the
lever stopper at 0% and 100%.
After re-installation, perform AUTO1
Re-install the positioner.
Ensure the feedback lever does not touch the
lever stopper at 0% and 100%.
After re-installation, perform AUTO1
07/2018