Herunterladen Inhalt Inhalt Diese Seite drucken

Circor SR-3300 Einbau- Und Betriebsanleitung Seite 42

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Einbau- und Betriebsanleitung
Installation and Operating instructions
6.3.1.1
AUTO1 Calibration (AUTO1)
AUTO1 changes zero and end points; however, KP, KI, KD will not be adjusted. It is recommended to perform AUTO1 when
the positioner has been set by the valve manufacturer already, and the field user wants to re-calibrate the positioner
<ENTER>
6 seconds
6.3.1.2
AUTO2
Calibration (AUTO2)
AUTO2 changes all of the parameters. It is recommended to perform AUTO2 when the positioner has been installed on the
valve for the first time.
<ENTER>
6 seconds
<ENTER>
6.3.2
Manual Mode (MANUAL)
Manual mode is used to maneuver valve stem manually. During "MANUAL", the positioner bypasses supply air to the actuator.
The movement of the stroke does not affect the positioner's save data valves.
<ENTER>
6 seconds
<DOWN>
<ENTER>
<UP>
Page 42
SR3300-8010
SR-3300
<ENTER>
<DOWN>
<ESC>
.
<ENTER>
<DOWN>
<ENTER>
07/2018

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für Circor SR-3300

Inhaltsverzeichnis