6.3.3.3
D value (Kd)
D value indicates the derivative value of the compensation signal based on the percentage of error allowance. As the value
increase, it is more likely to have hunting. As the value decreases, it can have poor linearity.
<UP>/<DOWN>
·
6.3.3.4
I value (KI)
I value indicates the additional compensation signal based on the percentage of error allowance. As the value increase, it is
more likely to have hunting. As the value decreases, the positioner will move slowly to the target position.
<UP><DOWN>
6.3.3.5
P_ (KP_), D_ (Kd_) , I_(KI_) values
P_, D_, and I_ values' principles are same as P, D, and I values, but these values will be activated when the error percentage
is within 1%.
6.3.4
Hand Calibration Mode (HAND CAL)
The positioner can be manually calibrated by entering into Hand Calibration Mode.
<ENTER>
<ENTER>
<ENTER>