7.
Error and Warning Code
7.1
Error code
Error Code
Code Description and Cause
Positioner is improperly installed.
Positioner is not parallel to the ground at 50%
MT ERR L
point. Lever is at lower position than actual
50% point.
Positioner is improperly installed.
Positioner is not parallel to the ground at 50%
MT ERR H
point. Lever is at higher position than actual
50% point.
Valve does not operate when positioner
CHK AIR
receive "Full Open" signal during the auto
calibration.
Operating angle is too small due to improper
RNG ERR
positioner installation.
Error of 10% or more persists more than 1 minute.
No valve movement.
C
High level of valve friction
Changes in setting pressure of actuator.
I-value reaches at maximum or minimum limit.
Changes in valve friction.
D
Changes in setting pressure of actuator.
Action
Re-install the positioner.
Ensure the feedback lever does not touch
the lever stopper at 0% and 100%.
Re-install the positioner.
Ensure the feedback leer does not touch
the lever stopper at 0% and 100%.
Check supply pressure level.
Adjust bracket so the positioner can be
mounted closer to actuator.
Perform BIAS calibration.
Check setting pressure of actuator.
Perform auto calibration.
Check setting pressure of actuator.