Herunterladen Inhalt Inhalt Diese Seite drucken

Circor SR-3300 Einbau- Und Betriebsanleitung Seite 41

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Einbau- und Betriebsanleitung
Installation and Operating instructions
6.3
Run Mode (RUN)
After power connection to the positioner, Run Mode will be appeared on positioner's LCD
screen within 6 seconds.
according to the receiving signal. There are six types of display message in "RUN" Mode.
9.
Run PV:
10. Run SV %:
11. Run SV mA:
12. Run MV:
13. Run Vel:
14. Run Err:
To change display, push <ESC> + <UP> buttons at the same time. The display will change in the order indicated above. If
<ESC> + <DOWN> pushed, the order will be appeared in opposite order. By pressing <ESC>, the display will return to "RUN"
mode.
6.3.1
Auto Calibration (AUTO CAL)
Auto Calibration (AUTO CAL) automatically calibrates the positioner. "AUTO CAL" process takes about 2~3 minutes, and the
duration of the process varies upon the size of the actuator. There are 3 types of AUTO CAL.
Zero Point
AUTO 1
O
AUTO 2
O
AUTO HF
O
BIAS
X
It is recommend to perform AUTO2 calibration for initial positioner
"RUN" indicates that the positioner adjusts the valve stroke
Process Value - valve stroke %
Set Value – input signal 0~100%
Set Value – input signal 4~20mA
Manipulate Valve – Motor Manipulate Value (digit)
Velocity – Current valve stem's velocity (digit)
Error – Difference between SV and PV (%)
End Point
KP, KI, KD
O
X
O
O
O
O
X
X
Page 41
SR3300-8010
SR-3300
RA / DA
BIAS
X
X
O
O
O
O
X
O
setting.
V_D
X
O
O
X
07/2018

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für Circor SR-3300