8.2

Testing distances

Notes:
The minimum distance from the detector is 75 cm (30").
At extreme temperatures, there is a 15% reduction in the testing
range.
8.2.1
Dräger FS 1100
Corresponding
Detection distance
flame detector
of the flame detector
in meters (feet)
Dräger Flame 2500
30 (100)
45 (150)
65 (215)
Dräger Flame 2570
40 (133)
60 (200)
90 (300)
Testing distance
in meters (feet)
15 (50)
2 (6.6)
6 (19.6)
9 (29.5)
12 (39.3)
20 (66)
4 (13)
8 (26)
12 (40)
15 (50)
8.2.2
Dräger FS 1200
Corresponding
Detection distance
flame detector
of the flame detector
in meters (feet)
Dräger Flame 2100
Dräger Flame 2350
Dräger Flame 2370
8.2.3
Dräger FS 1300
Corresponding
Detection distance
flame detector
of the flame detector
in meters (feet)
Dräger Flame 2000
8.2.4
Dräger FS 1400
Corresponding
Detection distance
flame detector
of the flame detector
in meters (feet)
Dräger Flame 2700
30 (100)
45 (150)
65 (215)
Technical data
Testing distance
in meters (feet)
15 (50)
10 (32.8)
15 (50)
3 (10)
20 (60)
10 (32.8)
Testing distance
in meters (feet)
15 (50)
1.2 (4)
Testing distance
in meters (feet)
15 (50)
2 (6.6)
6 (19.6)
9 (29.5)
12 (39.3)
en