NM24A-MF
Technical data
Safety notes
Product features
Mode of operation
Parameterisable actuators
Simple direct mounting
Manual override
High functional reliability
Adjustable angle of rotation
Home position
2
Damper actuator, parameterisable, Modulating,
AC/DC 24 V, 10 Nm
Safety
Protection class UL
Degree of protection IEC/EN
Degree of protection NEMA/UL
EMC
Certification IEC/EN
Certification UL
Mode of operation
Rated impulse voltage supply / control
Control pollution degree
Ambient temperature
Non-operating temperature
Ambient humidity
Maintenance
Weight
Weight approx.
• The device must not be used outside the specified field of application, especially not
!
in aircraft or in any other airborne means of transport.
• Outdoor application: only possible in case that no (sea)water, snow, ice, insolation
or aggressive gases interfere directly with the actuator and that is ensured that the
ambient conditions remain at any time within the thresholds according to the data
sheet.
• Only authorised specialists may carry out installation. All applicable legal or
institutional installation regulations must be complied during installation.
• The device may only be opened at the manufacturer's site. It does not contain any
parts that can be replaced or repaired by the user.
• Cables must not be removed from the device.
• To calculate the torque required, the specifications supplied by the damper
manufacturers concerning the cross-section, the design, the installation site and the
ventilation conditions must be observed.
• The device contains electrical and electronic components and must not be disposed
of as household refuse. All locally valid regulations and requirements must be
observed.
The actuator is connected with a standard modulating signal of DC 0...10V and drives
to the position defined by the positioning signal. Measuring voltage U serves for the
electrical display of the damper position 0...100% and as slave control signal for other
actuators.
The factory settings cover the most common applications. Single parameters can be
modified with the Belimo Service Tools MFT-P or ZTH EU.
Simple direct mounting on the damper spindle with an universal spindle clamp,
supplied with an anti-rotation device to prevent the actuator from rotating.
Manual override with push-button possible (the gear is disengaged for as long as the
button is pressed or remains locked).
The actuator is overload protected, requires no limit switches and automatically stops
when the end stop is reached.
Adjustable angle of rotation with mechanical end stops.
The first time the supply voltage is switched on, i.e. at the time of commissioning, the
actuator carries out a synchronisation. The synchronisation is in the home position
(0%).
The actuator then moves into the position defined by the positioning signal.
Y = 0 V
0
ccw
Y = 0 V
1
NM24A-MF • en-gb • 2015-09-30 • subject to changes
Änderungen vorbehalten
2018-01-30
l indab | Wi r v e re i nf ache n B au
RCW-1/RCWB-1
UL Class 2 Supply
IP54
NEMA 2, UL Enclosure Type 2
CE according to 2004/108/EC
IEC/EN 60730-1 and IEC/EN 60730-2-14
cULus according to UL 60730-1A, UL 60730-2-
14 and CAN/CSA E60730-1:02
Type 1
0.8 kV
3
-30...50°C
-40...80°C
95% r.h., non-condensing
Maintenance-free
0.82 kg
cw