Herunterladen Diese Seite drucken

Lindab RCW-Serie Montageanleitung Seite 11

Verstellbarer dralldurchlass

Werbung

Montageanleitung
Parmeterisable linear actuator for
adjusting dampers and slide valves in
technical building installations
• Air damper size up to approx. 1 m²
• Actuating force 150 N
• Nominal voltage AC/DC 24 V
• Control modulating DC (0)2...10 V
Variable
• Position feedback DC 2...10 V
Variable
• Length of Stroke Max. 60 mm,
adjustable in 20 mm increments
Technical data
Electrical data
Functional data
www.belimo.eu
Technical data sheet
Nominal voltage
Nominal voltage frequency
Nominal voltage range
Power consumption in operation
Power consumption in rest position
Power consumption for wire sizing
Connection supply / control
Parallel operation
Actuating force motor
Modifiable actuating force
Positioning signal Y
Positioning signal Y note
Control signal Y variable
Operating range Y
Operating range Y variable
Position feedback U
Position feedback U note
Position feedback U variable
Position accuracy
Direction of motion motor
Direction of motion note
Direction of motion variable
Manual override
Length of Stroke
Stroke limitation
Running time motor
Running time motor note
Motor running time variable
Adaption setting range
Adaption setting range variable
Override control
Override control variable
Sound power level motor
Safety
Protection class IEC/EN
Protection class UL
Degree of protection IEC/EN
Degree of protection NEMA/UL
LH24A-MF60 • en-gb • 2016-03-08 • subject to changes
Änderungen vorbehalten
2018-01-30
l indab | Wi r v e re i nf ache n B au
RCW-1/RCWB-1
AC/DC 24 V
50/60 Hz
AC 19.2...28.8 V / DC 21.6...28.8 V
2.5 W
1.2 W
5 VA
Cable 1 m, 4 x 0.75 mm²
Yes (note the performance data)
Min. 150 N
25%, 50%, 75% reduziert
DC 0...10 V
Input impedance 100 kΩ
Open-close
3-point (AC only)
Modulating (DC 0...32 V)
DC 2...10 V
Start point DC 0.5...30 V
End point DC 2.5...32 V
DC 2...10 V
Max. 0.5 mA
Start point DC 0.5...8 V
End point DC 2.5...10 V
±5%
Selectable with switch
Y = 0 V: with switch 0 (retracted) / 1 (extended)
Electronically reversible
With push-button, can be locked
Max. 60 mm, adjustable in 20 mm increments
can be limited on both sides with mechanical
end stops
150 s / 100 mm
corresponds to 90 s / 60 mm
70...270 s / 100 mm
manual
No action
Adaption when switched on
Adaption after pushing the gear disengagement
button
MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, AC only) = 50%
MAX = (MIN + 32%)...100%
MIN = 0%...(MAX – 32%)
ZS = MIN...MAX
45 dB(A)
III Safety extra-low voltage
UL Class 2 Supply
IP54
NEMA 2, UL Enclosure Type 2
LH24A-MF60
1
11