Herunterladen Diese Seite drucken

Lindab RCW-Serie Montageanleitung Seite 16

Verstellbarer dralldurchlass

Werbung

l in d a b | Wi r v ere i n fac h en B a u
Montageanleitung
LH24A-MF60
Operating controls and indicators
1
Adaption
Power
Status
4
5
Installation notes
!
Applications without transverse force
Applications with transverse forces
Service
Service Tools connection
16
6
Linear actuator, parameterisable, modulating,
AC/DC 24 V, 150 N
1
Direction of stroke switch
1
Switch over:
0
2
Push-button and LED display green
Off:
2
On:
Press button:
3
3
Push-button and LED display yellow
Off:
On:
Press button:
4
Gear disengagement button
Press button:
Release button:
5
Service plug
For connecting parameterisation and service tools
Check power supply connection
2
Off and
3
Notes
• If a rotary support and/or coupling piece is used, losses in the actuation force
losses are to be expected.
The linear actuator is screwed directly to the housing at three points. Afterwards, the
head of the gear rod is fastened to the moving part of the ventilation application (e.g.
damper or slide valve).
Connect the coupling piece with the internal thread (Z-KS2) to the head of the gear
rod. Screw the rotary support (Z-DS1) to the ventilation application. Afterwards, the
linear actuator is screwed to the previously mounted rotary support with the enclosed
screw. Afterwards, the coupling piece, which is mounted to the head of the gear rod, is
attached to the moving part of the ventilating application (e.g. damper or slide valve).
The transverse forces can be compensated for to a certain limit with the rotary support
and/or coupling piece. The maximum permissible swivel angle of the rotary support
and coupling piece is 10°, laterally and upwards.
The actuator can be parameterised by ZTH EU via the service socket.
For an extended parameterisation the PC tool can be connected.
AC 24 V
+
DC 24 V
1
2
3
5
Y
U
Änderungen vorbehalten
LH24A-MF60 • en-gb • 2016-03-08 • subject to changes
RCW-1/RCWB-1
Direction of stroke changes
No power supply or malfunction
In operation
Triggers stroke adaptation, followed by standard mode
Standard mode
Adaptation or synchronising process active
No function
Gear disengages, motor stops, manual override possible
Gear engages, synchronisation starts, followed by standard mode
On
Possible wiring error in power supply
Y
U
2018-01-30
ZTH EU
i
esc
OK
BELIMO
PC-Tool
USB
www.belimo.eu

Werbung