Verstellbarer dralldurchlass

Werbung

Montageanleitung
LH24A-MF60
Functions
Control with 4...20 mA via external resistor
– +
500
(–)
4...20 mA
(+)
U
DC 2...10 V
1
2
3
5
Y
U
Functions for actuators with specific parameters (Parametrisation with PC-Tool necessary)
Override control and limiting with AC 24 V with relay contacts
e
a
b
c
d
1
2
3
5
e.g. 1N 4007
Y
U
Control open-close
+
U
1
2
3
5
Y
U
www.belimo.eu
Linear actuator, parameterisable, modulating,
AC/DC 24 V, 150 N
Caution:
The operating range must be set to
DC 2...10 V.
The 500 Ω resistor converts the
4...20 mA current signal to a voltage
signal DC 2...10 V
Y (DC 0...10 V)
a
b
c
d
e
1)
Close
MIN
ZS
MAX
Open
Y
Control 3-point
U
a
b
e.g. 1N 4007
a
1
2
3
5
Y
U
LH24A-MF60 • en-gb • 2016-03-08 • subject to changes
Änderungen vorbehalten
RCW-1/RCWB-1
Functional check
– +
1
2
3
5
Y
U
Override control and limiting with AC 24 V with rotary switch
e.g. 1N 4007
1
2
3
5
Y
U
1
1
b
0
0
2018-01-30
l indab | Wi r v e re i nf ache n B au
Procedure
1. Apply 24 V to connection 1 and 2
2. Disconnect connection 3:
- for direction of stroke 0: Actuator
travels in the direction "retracted"
- for direction of stroke 1: Actuator
travels in the direction "extended"
3. Short circuit connections 2 and 3:
- Actuator runs in the opposite
direction
1) Caution: This function is only
guaranteed if the start point of the
operating range is defined as min.
0.5 V.