Herunterladen Diese Seite drucken

Lindab RCW-Serie Montageanleitung Seite 13

Verstellbarer dralldurchlass

Werbung

Montageanleitung
LH24A-MF60
Product features
High functional reliability
Home position
Adaption and synchronisation
Accessories
Electrical accessories
Mechanical accessories
Service Tools
www.belimo.eu
Linear actuator, parameterisable, modulating,
AC/DC 24 V, 150 N
The actuator is overload protected, requires no limit switches and automatically stops
when the end stop is reached.
The first time the supply voltage is switched on, i.e. at the time of commissioning, the
actuator carries out a synchronisation. The synchronisation is in the home position
(0%).
The actuator then moves into the position defined by the positioning signal.
Y = 0 V
1
Y = 10 V
0
An adaption can be triggered manually by pressing the "Adaption" button or with the
PC-Tool. Both mechanical end stops are detected during the adaption (entire setting
range).
Automatic synchronisation after pressing the gearbox disengagement button is
configured. The synchronisation is in the home position (0%).
The actuator then moves into the position defined by the positioning signal.
A range of settings can be adapted using the PC-Tool (see MFT-P documentation)
Description
Digital position indicator for front-panel mounting, 0...99%, front mass
72 x 72 mm
Range controller for wall mounting, adjustable electron. Min./max.
angle of rotation limitation
Positioner for wall mounting, range 0...100%
Positioner in a conduit box, range 0...100%
Positioner for front-panel mounting, range 0...100%
Positioner for wall mounting, range 0...100%
Connecting cable 5 m, A+B: RJ12 6/6, To ZTH/ZIP-USB-MP
Connection cable 5 m, A: RJ11 6/4, B: Free wire end, To ZTH/ZIP-
USB-MP
Description
End stop set for LH
Rotary support for compensation of transverse forces
Coupling piece M6 for LH, galvanised steel
Description
Service Tool, for MF/MP/Modbus/LonWorks actuators and VAV-
Controller
Belimo PC-Tool, software for adjustments and diagnostics
Adapter to Service Tool ZTH
Änderungen vorbehalten
LH24A-MF60 • en-gb • 2016-03-08 • subject to changes
2018-01-30
l indab | Wi r v e re i nf ache n B au
RCW-1/RCWB-1
Type
ZAD24
SBG24
SGA24
SGE24
SGF24
CRP24-B1
ZK1-GEN
ZK2-GEN
Type
Z-AS2
Z-DS1
Z-KS2
Type
ZTH EU
MFT-P
MFT-C
13
3

Werbung

loading

Diese Anleitung auch für:

Rcw-1Rcwb-1Rcw-2Rcwb-2Rcwb-serie