GSA 950-1200 Edelstahl_Layout 1 a4 14.12.18 08:59 Seite 10
of parts 10) with the control box (list of parts 16). Attention: this hose should not be extended, be-
cause otherwise a perfect on and off switch can not be guaranteed.
Installation of the inlet aperture:
1. Screw the 4 distance screws (list of parts 5 installation kit) in the appropriate thread. Note the-
refore fig. 1
marked with
2. Then connect the line for the air supply or for the on-off switch (Attention: Spring must be on
the hose) with the appropriate connections on the inlet aperture. fig 7. Use the clamping collet
(long/thin) to fix the air hose to the inlet aperture and act like in mounting the base unit point 5.
3. Insert the inlet aperture and fix it using 4 screws (list of parts 14).
4. If a round retainer is mounted, it replaces the flange.
Precautions for building companies
The pump shaft must have a minimum of 60 cm x 60 cm and a minimum depth of 100 cm. Fur-
thermore there must be a sufficient ventilation as well as a drain possibility for any leakage of
water.
For sealing the plastic thread exclusively a Teflon tape must be used.
All system components must be mounted in the way that they are voltage free and free of conta-
mination. In particular, the seat of all the o-rings, union nuts, etc. must be checked to that effect.
The pump must never run dry (which means without water), because otherwise the mechanical
seal will be damaged (loss of warranty).
The use in and around swimming pools or garden ponds is only permitted if they are built accor-
ding to local statutory regulations. In this regard please contact your Neptun expert or the local
bulding department.
assignment plan/ wiring diagram for Compact 950 fig. 8/9/10
There are rules necessarily to be observed by ÖVE (VDE), as well as the local EVU when installing
the system. The installation may exclusively be carried out by a licensed electrician. In power line
an all- pole seperator with a contact gap of at least 3 mm must be provided. In the power line a
residual current circuit breaker with a rated leakage current of <= 30 mA must be provided.
Attention! Pay attention to the motor direction of rotation (direction of rotation arrow)
The switching device ( list of parts 16) must be installed in a place easily accessible and dry. The
air suction valve must be above the level of the water surface. In the shaft there must be a suffi-
cient sized floor drain.
10
Betriebsanleitung GSA Compact 950/1200 Edelstahl V.20181129