Herunterladen Inhalt Inhalt Diese Seite drucken

Safety Precautions; Installation - Carrier 42DW serie Anweisungen Zur Installation

Ventilator-konvektoren hydronische global-satelliteinheit
Vorschau ausblenden Andere Handbücher für 42DW serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 6
Fan coil units "Hydronic Global Satellite"
Ref. Q.ty
1 Electric heater
1 Thermostat cover
1 Circuit diagram
2 Cover screws
2 Labels
1 Screw for relay
2 Instructions
1 Support flange
h
Fig.1
H
Outlet flange
Fig.3
Screw for relay
Power terminal block
E
Multicore faston terminal connector
F
Cable clamp
Z

Safety precautions

• WARNING: do not install heating element kit when the unit is
configured with lateral air outlets or octopus.
• Heating element kit can only be installed if the unit is configured
with a front air outlet. Maximum external static pressure is shown
in table 2.
• Read this instruction manual thoroughly before using the
heating element kit and keep it for further consultation even after

installation.

• This kit complies with low voltage (EEC/73/23), electromagnetic
compatibility (EEC/89/336) Directive.
• The installation must be carried out by a qualified installer.
• For safety reasons, installers are required to read the general
information carefully.
• Follow all the instructions below to ensure safety.
• Inspect the kit for damage due to improper transport. Do not
install or use damaged equipment.
• To prevent fire, explosion or injury, do not operate the unit
with kit near dangerous substances or close to naked light
equipment.
• Check that voltage and frequency of the mains power supply are
those required for the kit to be installed; the available power must
be adequate to operate any other appliances connected to the
same line.
• Make sure that properly sized disconnecting and safety switches
are installed.
Installation
• Disconnect the product from the mains power supply prior to installing
the kit.
• Loosen the fixing screws (fig. 1) and remove the outlet flange (ref.H).
• Fix the electric heater  to the unit outlet using the screws removed
previously (fig. 2 a-b).
• Remove the indicated area from the electric box (fig. 2 a-b).
• Place the relay inside the electric box and fix it using the screw  (fig.
3).
• Make electric connections as shown in the circuit diagram  and in
fig.3.
- Connect the blue cable (ref. Y) in the electric box to contact A1 of
relay coil (ref. A).
- Connect the orange cable (ref. X) of contact A2 of the relay coil (ref.
B) to terminal "H" of the 6 pole terminal block (ref. F).
- Connect the red cable of the thermostat (ref. K) to terminal L of the
power terminal block (ref. E).
Electric heater operating limit
Max. T of indoor air +27° C
Tabel 2
42DWC
Maximum outdoor static pressure [Pa]
07
09
12
16
• The manufacturer declines any liability for damage resulting
from modifications or errors in the electrical connections. Failure
to observe the installation instructions, or use of the kit under
conditions other than those indicated in the table "Operating
limits" of the unit/kit installation manual, will immediately
invalidate the unit warranty.
• All of the manufacturing and Packaging materials used for your
new appliance are compatible with the environment and can be
recycled.
• When installing the heating element kit and after connecting
the electric cables, cover the connectors using the protection
devices.
• In order to avoid electric shock, fire or injury, stop the kit and
disconnect the safety switch in case of abnormal events (such as
smell of burning) and call Carrier Service for further instructions.
• WARNING: Disconnect the mains power supply prior to any
maintenance operations or prior to handling any internal parts of
the kit.
• Do not attempt to repair, move, modify or re-install the kit on your
own. To avoid electric shock or fire make sure these operations
are carried out by qualified personnel only.
• Contact the qualified service if one of the following events takes
place:
- hot or damaged power supply cable; frequent operation of the
protection devices;
- unusual smell (such as smell of burning).
- Connect the black cable of the thermostat (ref. G) to contact 11 of
the relay (ref. C).
- Connect the blue cable of the electric heaters (ref. J) to terminal N
of the power terminal block (ref. E).
- Connect the black cable of the electric heaters (ref. I) to contact 14
of the relay (ref. D).
• When connections are all made, use the cable clamp (ref. Z) to fix the
cables from the electric heaters as shown in fig. 3.
• Make the electrical connection to the mains electricity supply using
the cable indicated in Table 1 and according to the circuit diagram .
• Make certain that the connection to the mains electricity supply is
made via an omnipolar switch with opening of contacts of at least
3mm.
• Close the electrical panel.
• Apply the characteristic label  supplied with the unit near the unit
label.
75
150
170
190
3

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

42dw903442dw9035

Inhaltsverzeichnis