3.5 Pumped fluids

Pumping unauthorised fluids
Dangerous for people and the environment!
➜ Only discharge authorised pumped fluids into the public sewerage
network.
Authorised pumped fluids:
The following liquids are allowed in discharge systems:
• Water contaminated by domestic use, human excrement, toilet roll.
Unauthorised pumped fluids:
The following liquids and substances are banned:
• Solid materials, fibres, tar, sand, cement, ash, coarse paper, hand towels, wipes, cardboard,
rubble, rubbish, slaughterhouse waste, oils, hydrocarbons, greases, etc.
• Wastewater containing harmful substances (for example, untreated greasy waste from restaurants).
Pumping these liquids and substances requires the fitting of a compliant grease trap.
• Rain water.

3.6 Installation of the SANIPUMP pumping station

• The characteristics shown on the rating plate have been compared with those on the order and
installation (supply voltage, frequency).
• The SANIPUMP
pumping station cannot be immersed in water of more than 5 m deep.
®
• The minimum height of the entries into the sump must be 500 mm with respect to the bottom of the
manhole.
• The installation room must be protected against frost.
• The installation room is adequately lit.
• The plant room where the SANIPUMP
allow a 600 mm clearance around and above the device to facilitate any maintenance operations.
• Stop valves must be fitted on the effluent inlet as well as on the discharge line, as close as possible
to the pumping station.
• Install a non-return valve on the pumping station outlet to prevent unintended start-up.
• The discharge line must be designed to prevent any back-flow of sewage.
• By fitting a non-return loop, located above the back-flow level, back-flow is avoided.
PLEASE NOTE: Unless otherwise specified locally, the back-flow level is the level of the
highway (roads, pavement, etc.). Extend this line after the non-return loop through a larger
diameter pipe.
• The pumped fluid is appropriate and authorised by this documentation (paragraph 3.5).
• In case of discharge of greasy effluents, the use of a degreasing tank is essential.
Wastewater other than those mentioned above, for example, of artisanal or industrial origin,
must not be discharged into the pipes without prior treatment.
WARNING
pumping station will be installed must be large enough to
®
®
23