Installation

6.3.3 Menu level 2: Low-voltage cut-off

The battery monitor protects the battery from discharging too low.
When the the battery monitor switches the device off, the battery only has
a proportion of its charging capacity. Avoid starting repeatedly or operating
electrical consumers. Ensure that the battery is recharged. As soon as the
required voltage is available, you can restart the system.
If the roof air conditioner only has the supply voltage set here, the system
is switched off.
➤ Start configuration mode (see chapter "Start and end configuration
mode" on page 32).
✓ The first digit of the display (see fig. 8 on page 5, Pos. 5) shows the
menu level and the second and third show the parameter which can
be set.
➤ Press the + button (see fig. 8 on page 5, 6) once to switch to menu le-
vel 2.
➤ Press the operating mode button (see fig. 8 on page 5, Pos. 4) to
change the parameter.
✓ The digits in the display flash until the parameter you enter is confir-
med.
➤ Press the + or - buttons (see fig. 8 on page 5, Pos. 6 and 7) to select
the value for the low voltage cut-off. The ID number displayed in the
second and third place of the digital display stands for the voltage at
which the system is switched off.
ID
number
➤ Press the operating mode button (see fig. 8 on page 5, Pos. 4) to
confirm your entry.
✓ The set value is saved and is then used when the system is restarted.
✓ You are now in menu level 2 and can use the + and - buttons to switch
between menu levels.
34
Low-voltage
cut-off
23,2
1
23,3
2
3
23,4
23,5
4
23,6
5
ID
Low-voltage
number
cut-off
23,7
6
23,8
7
8
23,9
24,0
9
24,1
10
CoolAir