5. WIRING

CAUTION
All the electrical connections must be carried out by qualified installers and all the wirings must be
connected according to the wiring diagram.
Make ground connection prior to any other electrical connections.
All power sources must be turned off before wiring work and do not turn on the power until you have
made sure all the wirings have been safety checked.
A main switch and circuit breaker or fuse must be installed, the capacity should be above 1.5 times of
maximum current in circuit.
An individual branch circuit and single socket used only for this appliance must be available.
Wire cross section is depending on the rated current and national, state and local electrical wiring
code. Consult local building codes and National electrical code for special requirement.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly
qualified persons in order to avoid a hazard.
The unit must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3mm in all poles. Installation of a residual current device (RCD) having
a rated residual operating current not exceeding 30mA is advisable.
5.1 POWER FROM OUTDOOR SIDE
Wiring figure
Indoor
Unit
Ground wiring
Power supply and connecting wires specification
Model(Btu/h)
Phase
Power
Supply
Frequency and volt
Rated Current
Fuse Rating(Field Supply)
Power Cord(Field Supply)
Indoor/outdoor connecting wiring
(Field Supply)
NOTE OF FUSE SPECIFICATIONS:
(applicalbe to units adpot R32 refrigerant only, and the fuse is made of ceramic.)
1. The specification of outdoor unit fuse is T20A/250VAC(for <24000Btu/h unit), T30A/250VAC(for
>24000Btu/h unit )
2. The specification of indoor unit fuse is T5A/250VAC, T10A/250VAC.
Power supply
Outdoor
Unit
High voltage wiring (Power supply)
Signal line
7k/9k/12k
1-Phase
220-240V~ 50Hz
220-240V~ 50Hz
10.0A
20A
2
H07RN-F; 3×2.5mm
H07RN-F; 3×2.5mm
2
H07RN-F; 4×1.5mm
H07RN-F; 4×1.5mm
Switch/Fuse
Power Cord
Ground wiring
18k
1-Phase
11.0A
20A
2
2
GB-14