Ventilation
1.
Set the master switch to position I
Switch on "Ventilation".
2.
Switch on "Ventilation".
Set master switch to position 0 "Off".

7. Installation guidelines

Prior to erection, it has to be ensured that the local supply conditions (type of gas and pressure) and
the present setting of the device match each other and that the local electric supply conditions
correspond to the electric data on the rating plate.
Installation regulations
During the setup of mobile WLEs with closed combustion chamber all local building, fire protection and
safety regulations have to be observed as a matter of principle.
Installation site
The devices must not be operated in locations, in which ignitable gas-air or dust-air mixtures may
occur (such as at filling stations, paint shops, et cetera).
Floors and ceilings have to be fire-retardant. The suction and exhaust vents must not be constricted.
Installation rooms
1. Setup of the WLE in closed, well-ventilated rooms with connection to a chimney:
-
The minimum room size has to correspond to an average heat requirement of the installation
room of 0.058kW/cum.
-
The required fresh air feed to ensure perfect combustion must be ensured by all means
(windows, doors or other openings).
Heat output
(kW)
25 kW
50 kW
80 kW
110 kW
140 kW
160 kW
2. Setup of the WLE in closed, well-ventilated rooms without connection to a chimney:
-
The minimum room size has to correspond to an average heat requirement of the installation
room of 0.058kW/cum.
-
A natural air replacement of 2.5 times of the volume capacity per hour has to be ensured as a
matter of principle (removal of combustion gases and supply of fresh air).
-
The following openings are required as a minimum for fresh air and outgoing air volumes:
Fresh air:
Exhaust air:
Main switch
Ventilation
OFF
HEATING
Socket for
room temperature
controller
Size of rooms
(m³)
500 m³
1000 m³
1400 m³
1900 m³
2500 m³
2800 m³
2.8 m³
2.8 m³
22
Push-button
Temperature limiter
Required volume of
fresh air (cum/h )
50 m³/h
80 m³/h
130 m³/h
180 m³/h
220 m³/h
240 m³/h