Herunterladen Diese Seite drucken

janitza UMG 96 RM-PN Installationsanleitung Seite 13

Differenzstrom-überwachung
Vorschau ausblenden Andere Handbücher für UMG 96 RM-PN:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

11
Residual current monitoring (RCM) via I5 and I6
Residual current monitoring (RCM) via I5 and I6
11
Operation and button functions
14
Operation and button functions
14
Connection variant of residual current monitoring
Connection variant of residual current monitoring
via current transformer
via current transformer
The device is operated with buttons 1 and 2,
The device is operated with buttons 1 and 2,
whereby the following distinctions are made:
whereby the following distinctions are made:
)
• Short press (button 1 or 2):
PE
N L1
• Short press (button 1 or 2):
Next step (+1).
Next step (+1).
• Long press (button 1 or 2):
• Long press (button 1 or 2):
previous step (-1).
previous step (-1).
The device differentiates between display and
The device differentiates between display and
programming mode.
programming mode.
I5
I5
Measured values are arranged in measured value
Measured values are arranged in measured value
I6
I6
display profiles and can be adjusted easily in the
display profiles and can be adjusted easily in the
GridVis® software (included). Measured value
GridVis® software (included). Measured value
display profile 1 is configured in the factory.
display profile 1 is configured in the factory.
Display mode
Display mode
• You can use buttons 1 and 2 to scroll between
• You can use buttons 1 and 2 to scroll between
the measured value indications.
the measured value indications.
• The measured value indication shows up to
• The measured value indication shows up to
C
C
3 measured values.
NOTE!
3 measured values.
NOTE!
• A time for an automatic indication change
• A time for an automatic indication change
The device
The device
between the measured value indications can be
• possesses no monitoring function and
between the measured value indications can be
• possesses no monitoring function and
configured in the GridVis® software.
configured in the GridVis® software.
does not send warnings itself!
does not send warnings itself!
• is designed to deliver measuring data
• is designed to deliver measuring data
to a PLC, which performs monitoring
to a PLC, which performs monitoring
C
C
NOTE!
functions if necessary.
NOTE!
functions if necessary.
More detailed information on operation, display and button functions for your device can be
More detailed information on operation, display and button functions for your device can be
found in the user manual.
found in the user manual.
Programming the current transformer
16
Programming the current transformer
16
1. Switch to programming mode.
1. Switch to programming mode.
2. The symbols for programming mode PRG
2. The symbols for programming mode PRG
Digital outputs
Digital outputs
and for the current transformer CT appear.
and for the current transformer CT appear.
2 and 3 optional digital outputs, semiconductor relays, not
2 and 3 optional digital outputs, semiconductor relays, not
3. Press button 1 - the first digit of the input
short-circuit proof.
3. Press button 1 - the first digit of the input
short-circuit proof.
field for the primary current flashes.
Switching voltage
field for the primary current flashes.
max. 33 V AC, 60 V DC
Switching voltage
Switching current
4. Use button 2 to select the value for the
max. 50 mAeff AC/DC
Switching current
4. Use button 2 to select the value for the
Response time
1st digit.
10/12 periods + 10 ms *
Response time
1st digit.
Pulse output (energy pulse)
max. 50 Hz
5. Use button 1 to move to the 2nd. digit.
Pulse output (energy pulse)
5. Use button 1 to move to the 2nd. digit.
* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms
6. Use button 2 to select the value of the
* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms
6. Use button 2 to select the value of the
2nd digit.
2nd digit.
Digital inputs
7. Use button 1 to move to the 3rd digit.
Digital inputs
7. Use button 1 to move to the 3rd digit.
3 optional digital inputs, semiconductor relays,
3 optional digital inputs, semiconductor relays,
8. Use button 2 to select the value of the
8. Use button 2 to select the value of the
not short-circuit proof.
not short-circuit proof.
3rd digit.
3rd digit.
Maximum counter frequency
20 Hz
Maximum counter frequency
9. Confirm with button 1.
9. Confirm with button 1.
18V .. 28 V DC
Input signal present
Input signal present
10. The complete number flashes.
10. The complete number flashes.
(typical 4 mA)
11. Use button 2 to select the decimal place and
0 .. 5 V DC,
11. Use button 2 to select the decimal place and
Input signal not present
Input signal not present
current less than 0.5 mA
thus the unit of the primary current.
thus the unit of the primary current.
12. Confirm with button 1.
12. Confirm with button 1.
13. The input range of the secondary current
13. The input range of the secondary current
Temperature measurement input
Temperature measurement input
flashes.
2 optional inputs.
flashes.
2 optional inputs.
Update time
14. Use button 2 to set the secondary current
1 second
Update time
14. Use button 2 to set the secondary current
(value 1 A or 5 A).
PT100, PT1000, KTY83,
(value 1 A or 5 A).
Connectable sensors
Connectable sensors
KTY84
15. Confirm with button 1.
15. Confirm with button 1.
Total burden (sensor + cable)
max. 4 kOhm
Total burden (sensor + cable)
16. Pressing buttons 1 and 2 simultaneously
16. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode.
(1. sec.) exits the programming mode.
Use button 2 to change to the input field for
Use button 2 to change to the input field for
the voltage transformer.
the voltage transformer.
The UMG 96 RM-PN measures AC currents,
The UMG 96 RM-PN measures AC currents,
pulsing direct currents and DC currents.
pulsing direct currents and DC currents.
Max. value, HT/reference
Max. value, HT/reference
The UMG 96 RM-PN measures residual currents
The UMG 96 RM-PN measures residual currents
Min. value NT/export
Min. value NT/export
in accordance with IEC/TR 60755 (2008-01), of
in accordance with IEC/TR 60755 (2008-01), of
L2 L3
PE
N L1
L2 L3
type A and
type A and
type B.
type B.
Suitable residual current transformers with
Suitable residual current transformers with
a rated current of 30 mA are connected to
a rated current of 30 mA are connected to
terminals 32 to 34 (I5) and terminals 35 to 37 (I6).
terminals 32 to 34 (I5) and terminals 35 to 37 (I6).
C
C
NOTE!
NOTE!
• The transformation ratios for the
• The transformation ratios for the
residual current transformer inputs
Export
residual current transformer inputs
Export
can be individually configured via
can be individually configured via
Load
Fig. Display UMG 96 RM-PN
Load
Fig. Display UMG 96 RM-PN
the GridVis® software (included).
the GridVis® software (included).
• A connection variant "UMG 96 RM-PN
• A connection variant "UMG 96 RM-PN
with residual current measurement
with residual current measurement
via measurement inputs I5/I6" can be
via measurement inputs I5/I6" can be
found in the user manual.
found in the user manual.
• Measurement inputs I5 and I6 do
• Measurement inputs I5 and I6 do
not require connection variants on
not require connection variants on
the device.
the device.
Serial interface
Serial interface
RS485 - Modbus RTU/Slave
RS485 - Modbus RTU/Slave
max. 33 V AC, 60 V DC
Stripping length
max. 50 mAeff AC/DC
Stripping length
10/12 periods + 10 ms *
Fig. "Current transformer" input area
Fig. "Current transformer" input area
max. 50 Hz
C
Ethernet connection
C
Ethernet connection
NOTE!
NOTE!
Connection
Connection
• Changes are only applied after exiting
• Changes are only applied after exiting
Conformance Class
programming mode.
Conformance Class
programming mode.
• For further information on current
• For further information on current
ProfiNet-Version
ProfiNet-Version
transformers and current transformer
transformers and current transformer
ProfiNet-Profile
ProfiNet-Profile
20 Hz
ratios, see the user manual.
ratios, see the user manual.
18V .. 28 V DC
(typical 4 mA)
C
C
NOTE!
NOTE!
0 .. 5 V DC,
Cable length (digital inputs and outputs,
Cable length (digital inputs and outputs,
current less than 0.5 mA
Programming voltage transformers:
Programming voltage transformers:
temperature measurement input)
temperature measurement input)
• Change to programming mode for the
• Change to programming mode for the
Up to 30 m
Up to 30 m
voltage transformer.
voltage transformer.
More than 30 m
More than 30 m
• The symbols PRG and VT appear in
• The symbols PRG and VT appear in
the display.
the display.
1 second
• The procedure for the voltage
• The procedure for the voltage
PT100, PT1000, KTY83,
KTY84
transformer programming is analogous
transformer programming is analogous
max. 4 kOhm
to that of the current transformer.
to that of the current transformer.
Further information on voltage transformers
Further information on voltage transformers
and voltage transformer ratios can be found
and voltage transformer ratios can be found
in the user manual.
in the user manual.
12
Establish the connection to the PC
12
Programming mode
15
15
Communication connections:
• Press and hold buttons 1 and 2 simultaneously
1.
1.
PC
(GridVis)
for 1 second to switch between display mode
PLC
Mean value
Mean value
and programming mode. The text PRG
appears in the display.
Direct connection of
Programming
Programming
the device to a PC/PLC
mode
• Configure the necessary settings for the
mode
Summation
with Ethernet/ProfiNet.
Summation
operation of the device in programming mode.
measurement
measurement
• The programming mode can be protected with
Phase conductor -
Phase conductor -
2.
2.
PC
Phase conductor
(GridVis)
Phase conductor
a user password.
PLC
Password
• Button 2 switches between the programming
Password
CT: Current
menus:
CT: Current
transformer
transformer
1. Current transformer
VT: Voltage
VT: Voltage
Connection of the device to a PC/PLC with Ethernet/ProfiNet
2. Voltage transformer
transformer
transformer
via a switch (fieldbus level).
K1: Output 1
3. Parameter list
K1: Output 1
K2: Output 2
K2: Output 2
3.
3.
4. TCP/IP device address
PC
(GridVis)
5. Subnet mask
Button 2
Button 2
6. Gateway address
Button 1
Button 1
Device connection with a PC via an
The device switches from programming mode to
interface converter.
display mode if
• no buttons are pressed for 60 seconds.
4.
4.
PC
• buttons 1 and 2 are pressed simultaneously for
(GridVis)
1 second.
Connection of the device to a PC via a
UMG 604 as a gateway.
C
More information on device configuration and
communication is provided as of step 14.
Current transformer,
Current transformer,
primary
primary
Manual TCP/IP configuration via the Ethernet interface
17
17
Programming mode
Programming mode
C
Unit indicator
Unit indicator
Terminal connection capacity (power supply voltage)
Current transformer,
Current transformer,
Conductors to be connected.
secondary
secondary
9.6 kbps, 19.2 kbps,
9.6 kbps, 19.2 kbps,
Only one conductor can be connected per terminal!
Current transformer
Each device within an Ethernet network has a unique
38.4 kbps, 57.6 kbps,
Current transformer
38.4 kbps, 57.6 kbps,
Single core, multi-core,
115.2 kbps
symbol
115.2 kbps
symbol
TCP/IP address. The TCP/IP address is assigned
fine-stranded
7 mm
7 mm
manually on the device.
Terminal pins, core end sheath
The 4-byte-long device address (Byte 0 to 3) is
Tightening torque
appended within the TCP/IP configuration with the
Stripping length
subnet mask and gateway details.
RJ45
RJ45
Manual configuration (example) of the TCP/IP
B - Switch class (IRT)
B - Switch class (IRT)
device address (Addr):
Terminal connection capacity (residual current or
2.2
2.2
1. Switch to programming mode.
temperature measurement inputs and digital inputs /
PROFIenergy V1.1,
PROFIenergy V1.1,
2. The symbols for programming mode PRG and for
outputs)
Entity Class 2
Entity Class 2
Single core, multi-core,
the current transformer CT appear.
fine-stranded
3. Pressing button 2 3 times takes you to the TCP/
Terminal pins, core end sheath
IP settings.
Tightening torque
(Press the subnet mask 4x and the gateway 5x)
Stripping length
Unshielded
Unshielded
4. Use button 1 to select the 1st digit of byte 0
Shielded
Shielded
(selection flashes).
5. Use button 2 to select the value.
Terminal connection capacity (serial interface)
6. Use button 1 to move to the 2nd. digit / 3rd. digit.
Single core, multi-core,
7. Use button 2 to select the corresponding value.
fine-stranded
8. Use button 1 to move to byte 1.
Terminal pins, core end sheath
9. Select bytes 1 to 3 in the same way.
Tightening torque
10. Configure the subnet mask (display SUb) and
Stripping length
gateway address (display GAt) in the same way.
13 / 16
Establish the connection to the PC
Programming mode
Communication connections:
• Press and hold buttons 1 and 2 simultaneously
C
Ethernet/Profinet
UMG 96
PC
Ethernet/Profinet
UMG 96
(GridVis)
for 1 second to switch between display mode
RM-PN
PLC
RM-PN
and programming mode. The text PRG
Direct connection of
appears in the display.
UMG 96
UMG 96
the device to a PC/PLC
Ethernet/Profinet
Ethernet/Profinet
• Configure the necessary settings for the
RM-PN
RM-PN
with Ethernet/ProfiNet.
operation of the device in programming mode.
• The programming mode can be protected with
PC
UMG 96
(GridVis)
UMG 96
a user password.
RM-PN
PLC
RM-PN
C
• Button 2 switches between the programming
Ethernet/Profinet
Ethernet/Profinet
Ethernet/Profinet
Ethernet/Profinet
menus:
Switch
Switch
1. Current transformer
Connection of the device to a PC/PLC with Ethernet/ProfiNet
2. Voltage transformer
via a switch (fieldbus level).
3. Parameter list
4. TCP/IP device address
RS232
RS232
RS485
RS485
UMG 96
UMG 96
PC
(GridVis)
5. Subnet mask
RM-PN
RS485
RM-PN
RS485
Recommendation for the Ethernet connection:
6. Gateway address
Use at least a CAT5 cable!
Device connection with a PC via an
UMG 96
UMG 96
RS485
RS485
The device switches from programming mode to
interface converter.
RM-PN
RM-PN
display mode if
• no buttons are pressed for 60 seconds.
Ethernet
RS485
UMG 96
Ethernet
RS485
UMG 96
UMG 604
UMG 604
• buttons 1 and 2 are pressed simultaneously for
PC
(GridVis)
RM-PN
RM-PN
In order to make the following settings, sample
1 second.
settings for the device and the PC are selected:
Connection of the device to a PC via a
Device IP address: 192.168.1.116
UMG 96
UMG 96
RS485
RS485
UMG 604 as a gateway.
RM-PN
RM-PN
Subnet mask:
C
NOTE!
NOTE!
PC IP address:
More information on device configuration and
Changes are only applied after exiting
Changes are only applied after exiting
Subnet mask:
communication is provided as of step 14.
programming mode.
programming mode.
Manual TCP/IP configuration via the Ethernet interface
C
NOTE!
NOTE!
The following steps are omitted with configuration of the device in a ProfiNet system (with DCP).
The following steps are omitted with configuration of the device in a ProfiNet system (with DCP).
Terminal connection capacity (power supply voltage)
Conductors to be connected.
Only one conductor can be connected per terminal!
Each device within an Ethernet network has a unique
Single core, multi-core,
0.2 - 2.5 mm
, AWG 26-12
TCP/IP address. The TCP/IP address is assigned
0.2 - 2.5 mm
2
, AWG 26-12
2
fine-stranded
manually on the device.
0.2 - 2.5 mm
Terminal pins, core end sheath
0.2 - 2.5 mm
2
2
The 4-byte-long device address (Byte 0 to 3) is
0.4 - 0.5 Nm
Tightening torque
0.4 - 0.5 Nm
appended within the TCP/IP configuration with the
7 mm
Stripping length
7 mm
subnet mask and gateway details.
Manual configuration (example) of the TCP/IP
device address (Addr):
Terminal connection capacity (residual current or
1. Switch to programming mode.
temperature measurement inputs and digital inputs /
2. The symbols for programming mode PRG and for
outputs)
the current transformer CT appear.
Single core, multi-core,
0.2 - 1.5 mm
2
, AWG 28-16
0.2 - 1.5 mm
2
, AWG 28-16
fine-stranded
3. Pressing button 2 3 times takes you to the TCP/
0.2 - 1.5 mm
2
Terminal pins, core end sheath
0.2 - 1.5 mm
2
IP settings.
0.2 - 0.25 Nm
Tightening torque
0.2 - 0.25 Nm
(Press the subnet mask 4x and the gateway 5x)
7 mm
Stripping length
7 mm
4. Use button 1 to select the 1st digit of byte 0
(selection flashes).
5. Use button 2 to select the value.
Terminal connection capacity (serial interface)
6. Use button 1 to move to the 2nd. digit / 3rd. digit.
Single core, multi-core,
0.2 - 1.5 mm
2
, AWG 28-16
7. Use button 2 to select the corresponding value.
0.2 - 1.5 mm
2
, AWG 28-16
fine-stranded
8. Use button 1 to move to byte 1.
0.2 - 1.5 mm
2
Terminal pins, core end sheath
0.2 - 1.5 mm
2
9. Select bytes 1 to 3 in the same way.
0.2 - 0.25 Nm
Tightening torque
0.2 - 0.25 Nm
10. Configure the subnet mask (display SUb) and
7 mm
Stripping length
7 mm
gateway address (display GAt) in the same way.
C
NOTE!
NOTE!
The TCP/IP device address is configured
The TCP/IP device address is configured
directly on the device (see step 17).
directly on the device (see step 17).
The device is also equipped with
The device is also equipped with
dynamic TCP/IP addressing (DCP) for
dynamic TCP/IP addressing (DCP) for
ProfiNet systems!
ProfiNet systems!
C
NOTE!
NOTE!
The following section explains the
The following section explains the
programming menus for the current
programming menus for the current
transformer (1.), TCP/IP device address,
transformer (1.), TCP/IP device address,
subnet mask and gateway address (4., 5., 6.)
subnet mask and gateway address (4., 5., 6.)
via the Ethernet interface, which are most
via the Ethernet interface, which are most
important for a installation manual.
important for a installation manual.
Recommendation for the Ethernet connection:
The Dynamic Configuration Protocol
The Dynamic Configuration Protocol
Use at least a CAT5 cable!
(DCP) distributes the addresses and
(DCP) distributes the addresses and
names within ProfiNet systems!
names within ProfiNet systems!
m
The UMG 96 RM-PN prioritises DCP.
m
The UMG 96 RM-PN prioritises DCP.
Damage to property due to
Damage to property due to
incorrect network settings
incorrect network settings
CAUTION!
In order to make the following settings, sample
CAUTION!
Incorrect network settings can cause faults in
settings for the device and the PC are selected:
Incorrect network settings can cause faults in
the IT network!
Device IP address: 192.168.1.116
the IT network!
255.255.255.0
Obtain information from your network
Subnet mask:
255.255.255.0
Obtain information from your network
administrator about the correct Ethernet
PC IP address:
192.168.1.117
192.168.1.117
administrator about the correct Ethernet
255.255.255.0
network settings for your device(s).
Subnet mask:
255.255.255.0
network settings for your device(s).
Terminal connection capacity (current measurement)
Terminal connection capacity (current measurement)
Conductors to be connected.
Conductors to be connected.
Only one conductor can be connected per terminal!
Only one conductor can be connected per terminal!
Single core, multi-core,
Single core, multi-core,
Designation
0.2 - 2.5 mm
, AWG 26-12
Designation
0.2 - 2.5 mm
2
, AWG 26-12
2
fine-stranded
fine-stranded
Terminal pins, core end sheath
0.2 - 2.5 mm
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Byte identifier
Byte identifier
2
Tightening torque
0.4 - 0.5 Nm
Tightening torque
of the address (e.g. Byte 0)
0.4 - 0.5 Nm
of the address (e.g. Byte 0)
Stripping length
Stripping length
7 mm
7 mm
Address value, Byte 0
Address value, Byte 0
Fig. TCP/IP address,
Fig. TCP/IP address,
Terminal connection capacity (voltage measurement)
Terminal connection capacity (voltage measurement)
Byte 1, value 168.
Byte 1, value 168.
Conductors to be connected.
Conductors to be connected.
Only one conductor can be connected per terminal!
A TCP/IP address consists
Only one conductor can be connected per terminal!
A TCP/IP address consists
Single core, multi-core,
of 4 bytes with the following
Single core, multi-core,
of 4 bytes with the following
0.08 - 4.0 mm
2
, AWG 28-12
0.08 - 4.0 mm
2
, AWG 28-12
fine-stranded
fine-stranded
structure (example):
structure (example):
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Tightening torque
0.4 - 0.5 Nm
Byte 0
Byte 1
Byte 0
Byte 2 Byte 3
Byte 1
Byte 2 Byte 3
Stripping length
xxx.xxx.xxx.xxx
7 mm
Stripping length
xxx.xxx.xxx.xxx
7 mm
192,168,001,116
192,168,001,116
C
C
NOTE!
NOTE!
Fig. TCP/IP address,
Fig. TCP/IP address,
Further technical data can be found in the
Further technical data can be found in the
Byte 2, value 001.
Byte 2, value 001.
user manual for the device.
user manual for the device.
Fig. TCP/IP address,
Fig. TCP/IP address,
Byte 3, value 116.
Byte 3, value 116.
13
18

Werbung

loading