Input function
4.Tank
Adjust the tank volume with [+] / [-] (100%). The default
volume
setting is 0 L. The value must be set.
5.Tank
Enter inner tank height in millimetres: e. g.: 249 cm
height
(max. value = 999,9 cm) (height without dome)
5b.Filling
Set the filling limit of the tank with [+]/ [-]:
limit
With fuel oil tanks, that is the shut-off point of the limit
indicator. The default setting is 95%.
e.g. 95%=237cm. For tanks which can be filled to the
very top (e.g. water tanks), it is necessary to set the
highest value of 99%.
6.View
In the 1st line of the display, the tank name/medium and
contents are displayed (e.g. in litres).
The display in the 2nd line can be selected:
View details
For fuel oil tanks in Germany, a free capacity display is
required according to TRwS 791-2. This is possible with
selection a) and b).
Steps 7 is only required for SmartBox
Entering incorrect switching points and mixing up the switch-on and shut-off
point can lead to the overfilling of the tank or the dry running of a pump!
Menu
7.Relay
7.Relay 1
SmartBox 2
or
7.Beeper
acoustic
alarm
SmartBox 3
part no. 28 100 57 f
Please see a volume table for the highest value,
if available. For a 100 m³ cyl. buried tank, this
may for example be the value 100600 litres.
Please see a volume table for the highest value,
if available. For a 100 m³ cyl. buried tank, this
may for example be the value 288 cm.
Input function
Switch function of relay 1 or beeper (acoustic alarm):
Deactive
The relay does not switch
Active
The relay switches
Example of switch point setting for Active (with
hysteresis):
Enter switching points as % values from 01-99 (and/or
enter as °C value from -99 to +99 only for probe with
temperature measurement)
Deactive  activate with [+] / [-] to
Active
 press Enter to confirm 
Switch-on 10%
Switch-off 12%
Switch-on +0°C
Switch-off +0°C  set with [+] / [-]  [Enter]
Deactivate the relay or beeperr via Deactive or input
of 0% or 0°C (for Switch-on and -off).
®
SmartBox
1 / SmartBox
Fillspace+Percent
Fillspace+Level
Percent+Level
®
2 and SmartBox
 set with [+] / [-]  [Enter]
 set with [+] / [-]  [Enter]
 set with [+] / [-]  [Enter]
®
2 / SmartBox
Input value
___________L
_________mm
__________%
____________
a)
b)
c)
®
3.
Input value
on ______%
off ______%
on ______°C
off ______°C
®
3
11 / 20

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Verwandte Produkte für GOK SmartBox 1

Diese Anleitung auch für:

Smartbox 3Smartbox 2

Inhaltsverzeichnis