Safety Notes; Correct Use; Transport, Storage And Packaging; Transport Inspection - oventrop Regumat Einbau- Und Betriebsanleitung

Vorschau ausblenden Andere Handbücher für Regumat:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2 Safety notes

2.1 Correct use

Safety in operation is only guaranteed if the connection
group "Regumat" is used correctly.
The "Regumat" connection group allows the con-
nection of a heat pump to the heating system and/or
a buffer storage cylinder.
Any use of the connection group outside of the above
applications will be considered as non-compliant and
misuse. Claims of any kind against the manufacturer
and/or his authorised representatives due to damages
caused by incorrect use cannot be accepted.
The observance of the installation and operating in-
structions is part of the compliance terms.
2.2 Possible dangers at the installation location
and during transport
The case of an external fire has not been taken into
consideration when constructing the heat pump con-
nection group "Regumat".
WARNING
Heavy product assembly
Risk of injury Suitable transport and lifting devices
are to be used. Wear suitable protective clothing
(e.g. safety shoes) during installation and use safety
devices. External components like handwheels or
pressure test points must not be misused for the
absorption of external forces, e.g. as connection
point for lever tools etc.
Hot and cold surfaces
Risk of injury Only touch with safety gloves and
inactivate installation before work commences.
Sharp edges
Risk of injury Only touch with safety gloves. Thre-
ads, bore holes and edges are sharp.
Small pieces
Risk of ingestion Store and install the small pieces
supplied with the connection group out of reach of
children.
Allergies
Health hazard Do not touch the connection group
and avoid any contact if allergies against the used
materials are known.
8
3 Transport, storage and
packaging

3.1 Transport inspection

Upon receipt check delivery for any damages caused
during transit.
Any damage must be reported immediately upon re-
ceipt.
3.2 Packaging
Packaging material is to be disposed of environmen-
tally friendly.

4 Technical data

4.1 Performance Data

Nominal size
Max operating temperature
for standard pumps
Max. operating temperature
for high-efficiency pumps
Max. operating pressure
kvs value
Opening pressure
check valve
Distance between
pipe centres
Connections
Fluids: Non-aggressive fluids (e.g. water and suitable
water and glycol mixtures according to VDI 2035). Not
suitable for steam, oily and aggressive fluids.
DANGER
Suitable measures (e.g. safety valves) have to be
taken to ensure that the maximum operating pres-
sures and maximum and minimum operating tem-
perature are not exceeded or undercut.
4.2 Materials
Valves:
Pump:
Wall bracket:
Insulation:
Seals:
Flanged pipe (optional): copper
DN 25
110°C
85°C
10 bar PN10
7.4
20 mbar
125 mm
G 1½ flat sealing
brass
body made of cast iron
at the top:
PA 6.6
at the bottom: galvanised
sheet steel
expanded polypropylene
EPDM