Functional Description - Honeywell BA295 Einbauanleitung

Systemtrenner
Vorschau ausblenden Andere Handbücher für BA295:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
1. Safety Guidelines
1. Follow the installation instructions.
The factory-set position of the ball valves may
not be altered. Non-compliance with this
instruction will make any warranty claims null
and void.
2. Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the
applications detailed in these installation instruc-
tions. Any other use will not be considered to comply
with requirements and would invalidate the
warranty.
4. Please take note that any assembly, commis-
sioning, servicing and adjustment work may only be
carried out by authorized persons.
5. Immediately rectify any malfunctions which may
influence safety.

2. Functional description

BA type backflow preventers are divided into three
pressure zones. The pressure in zone
in zone
, which in turn is higher than in zone
discharge valve is connected to zone
at the latest when the differential pressure between
zones
and
falls to 0.14 bar. The water from zone
discharges to atmosphere. In this way the danger of
back pressure or back syphonage into the supply
network is prevented. The pipework connection is
interrupted and the drinking water network is
protected.
3. Application
Medium
Maximum inlet
pressure
Minimum inlet pressure 1.5 bar
4. Technical data
Installation position Horizontal with discharge valve
downwards
Max. operating
temperature
65°C
Discharge pipe
DN50 for connection sizes
connection
DN70 for connection sizes 1
1
Connection size
/
" - 2"
2
MU1H-1220GE23 R0809
is higher than
. A
which opens
Water
10.0 bar
1
/
" - 1"
2
1
/
" - 2"
4
GB
5. Scope of delivery
The backflow preventer consists of:
• Housing
• Integral strainer, mesh size approx. 0.6 mm
• Valve cartridge with integral check valve and
discharge valve
• Outlet check valve
• Three ball valves for the connection of a differential
pressure gauge
• Connection fittings
• Discharge connection
6. Options
BA295-... A = Standard version with threaded
connections
BA295-... B = Standard version with threaded
connections
1" and 1
Connection size
7. Assembly
7.1 Installations Guidelines
• Install shutoff valves before and after backflow
preventer
• Install in horizontal pipework with the discharge
valve downwards
• Ensure good access
o Simplifies maintenance and inspection
• Backflow preventers of this type have an integral
strainer which protects the device from the ingress
of dirt. With highly polluted water a fine filter should
be installed upstream to ensure the correct function
of the device.
• Do not install in places where flooding can occur
• The installation environment should be protected
against frost and ventilated well
• Install discharge pipework which has adequate
capacity
Use and type of installation according to
DIN EN 1717
6
1
3
1
/
",
/
", 1
/
" und 2"
2
4
2
1
/
"
4