8.2
Connecting the inverter to the battery
Warning
Do not reverse the polarity. Reversing the polarity of the battery
connections will cause a great spark and the fuses will melt.
The fuses should only be replaced by an electrician.
Warning
Make sure that neither the battery nor any consumer units are
connected to the inverter while you are connecting it.
Note
Tighten the nuts and bolts to a torque of 12 – 13 Nm. Loose con-
nections may cause overheating.
➤ Set the main switch (6 2, page 4) to "Off".
Required cable cross
section
25 mm²
15 mm²
35 mm²
25 mm²
35 mm²
25 mm²
70 mm²
55 mm²
110 mm²
70 mm²
Connecting the inverter
Cable fuse
(2 B, page 3)
100 A
50 A
200 A
100 A
200 A
100 A
250 A
150 A
400 A
250 A