Transducer with a linear characteristic
input unipolar +4 mA to + 20 mA
output unipolar 0 to +A
BR11.1 – BR 11.2 : closed
BR12.1 – BR 12.2 : open
X14.1 – X14.2 : closed
Zero adjustment
Apply E = 4 mA ± 0.05 % E
trimming potentiometer R41 .
End value
Apply E = 20 mA ± 0.05 % E
trimming potentiometers R42.
Check the intermediate values.
Transducer with a linear characteristic
input unipolar +4 mA to +12 mA to +20 mA
output symmetrically bipolar -20 mA to 0 to +20 mA
BR11.1 – BR11.2 : closed
BR12.1 – BR12.2 : open
1. Zero adjustment
X14.1 – X14.2: open
Apply E = +4 mA ± 0.05 %, set the output value to A = 0 mA ± 0.1 % with
trimming potentiometer R41.
Set output value
X14.1 – X14.2 : open
Apply E = +12 mA ± 0.05 %, set the output value to A = +20 mA ± 0.1 % with
trimming potentiometer R42.
2. Zero adjustment
X14.1 – X14.2 : closed
Apply E = +12 mA ± 0.05 %, set the output value to A = 0 mA ± 0.1 % with
trimming potentiometer R41.
Check output value
X14.1 – X14.2 : closed
Apply E = +20 mA ± 0.05 %,
check output value A = +20 mA ± 0.1 %.
Apply E = +4 mA ± 0.05 %,
check output value A = -20 mA ± 0.1 %.
Check the intermediate values.
N
BR11.2 – BR11.3 : open
, set the output value to A = 0 ± 0.1 % A
N
, set the output end value to A = A
N
BR11.2 – BR11.3: open
SIMEAS-T - Transducer with Auxiliary Power
± 0.1 % A
N
with
N
with
N
41