Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data; Correct Use - Oventrop Rbg-C K Installationsanleitung

Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

EN
Read installation instructions and operating manual in their
entirety before installing the room controller "RBG-C K"
and the accessory components! Both documents are avail-
able as PDF file for download on the Oventrop "DynaTemp"
central unit. The instructions of the respective system must
be observed.
Installation, initial operation, maintenance and repairs have
to be carried out by authorised and qualified tradesmen
according to established laws and regulations!
The installation and operating instructions of the respective
"DynaTemp" system as well as all other valid documents
such as this short guide have to remain with the user of the
system!
Content
1

Technical data

2

Correct use

3
Dimensions
4
Installation
5
Pin assignment
6
Examples of connection
Illustr. 1.1 Wired room controller "RBG-C K"
OVENTROP GmbH & Co. KG
Paul-Oventrop-Straße 1
D-59939 Olsberg
Phone
+49 (0) 29 62 82-0
Fax
+49 (0) 29 62 82-400
E-Mail
mail@oventrop.de
Internet www.oventrop.com
For an overview of our global presence
visit www.oventrop.de.
1
Technical data
Electrical connection:
Power supply: AC 24 V ± 10%, 50 ...60 Hz
Power consumption (without actuators): < AC 1.8 VA
Bus load: < 6 mA
Note!
The power consumption of the connected actuators (observe
start up loads) has to be considered when selecting the
transformer, conductor cross section and cable paths.
Communication:
C-bus: twisted, shielded data cable
(two cores with min. 0.5 mm²)
1
Inputs:
1
Digital: for the connection of a volt free contact
2
(wired window contact or movement sensor)
2
Outputs:
2
Analogue: 1× AO DC 0 ...10 V, max. 10 mA (for steady
2
actuators)
Digital: 1× DO triac AC 24 V, max. 1.2 A (for two point actuators)
Power supply via the electric connection,
Terminal 1 and terminal 2 (AC 24V)
Operating conditions:
Temperature: 0 ...+50 °C
Humidity: 5 ...95 % R.H., not condensing (DIN EN 61131-2)
Storage conditions:
Temperature: -20 ...+70 °C
Humidity: 5 ...95 % R.H., not condensing (DIN EN 61131-2)
Housing:
Dimensions: 84.5 × 84.5 × 25 (L x W x H in mm)
Approx. weight: 70 g
Type of installation: surface-mounting
Installation directly onto the wall (cabling through the reverse
side) or onto a standard flush socket (screw fastening Ø 60).
(The lower part can be pre-assembled and connected
separately from the upper part.)
Material / colour: plastic ABS, pure white (RAL 9010)
Protective system: III, protective low voltage
Protection: IP 20
Measuring element internal temperature: PT 1000 1/3 DIN B
Measuring range: -35 ...+100 °C
Resolution: 0,1°
Tolerance: ± 0,5 K
2
Correct use
The design intent of the room controller "RBG-C K" is as an
electrical interface between actuators, movement sensor and
window contacts and the central unit "DynaTemp" via a bus line.
The room temperature is modified with the help of a rotary knob.
Any use of the room controller "RBG-C K" outside the above
applications will be considered as non-compliant and misuse.
Claims of any kind against the manufacturer and/or his author-
ised representative due to damages caused by incorrect use
cannot be accepted.
The observance of the enclosed documents is part of the
compliance terms.
This short guide is for information purposes only.
Valves, controls + systems
"DynaTemp";
Short guide for the specialised installer
Subject to technical modifications without notice.
115327181 05/2017