OPERATION

• Use this product only when you have carefully read the assembly and operating
manual.
• For your own safety, observe all the safety messages in this assembly and operating
manual.
• Please also consider the safety of others.
The product can be damaged if the gas cylinder is moved!
Entrained liquid phase can cause the pressure to increase in the LPG system and damage
the product or the LPG system.
Do not move the gas cylinder while the system is in operation.

TROUBLESHOOTING

Fault cause
Gas smell
Leaking LPG is extremely
flammable.
Can cause explosions.
Abnormal flame pattern of
non-adjustable pressure
regulator
The display unit of the safety
pressure regulator S2SR
(OPC) is set to RED
No gas flow.
Low-pressure regulator type EN61-DS PS 16 bar
Action
 Close the gas supply.
 Do not use any electric switches.
 Do not use a phone in the building.
 Ventilate rooms well.
 Shut down the LPG system.
 Contact a specialised company.
Compare the nominal outlet pressure with the nominal
connection pressure:
 if they do not correspond, replace the pressure regulator
or the gas appliance
Measure the outlet pressure; outlet pressure is not within
the specified limits:
 check the system configuration
 pressure regulator is defective, replace
Safety pressure regulator S2SR (OPC) reacted:
 switch off gas supply
 allow short bursts of gas to escape from the gas
equipment to achieve pressure equalisation
 if no pressure equalisation is achieved, replace the
pressure regulator
Gas supply is closed:
 open the gas cylinder valve, shut-off fittings, or excess
flow valve EFV (SBS)
The thermal shut-out device has responded:
 replace the pressure regulator
The excess flow valve EFV (SBS) has responded:
 check the entire LPG system for leaks
 upon completion of leak testing, you can put the
pressure regulator into service again
Filter screen in the inlet connection is dirty:
 send the pressure regulator to the manufacturer to be
checked