Wiring the device modules
Memory modules
Fig. 7−2
S220
Fig. 7−3
Via the DIP switches on the front, you can set:
the node address (labelling "1" ... "64") and
ƒ
baud rate (labelling "a" ... "d")
ƒ
)
Note!
If DIP switches 1 ... 64 = OFF ("Lenze setting"): When the standard device is
switched on, the parameterisation of codes C00350 (node address) and
C00351 (baud rate) is activated.
Switch the voltage supply of the standard device off and then on again to
activate altered settings.
Setting the node address
The node address of the drive is calculated from the sum of all address switches in the "ON"
position.
Setting the baud rate
d
c
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
80
Memory module with DIP switch (as of order designation E94AYM22)
O
N
d
c
b
a
64
32
16
8
4
Baud
CAN Address
Arrangement and labelling of the DIP switches
b
a
Baud rate
ON
OFF
10 kbps
OFF
ON
20 kbps
ON
ON
50 kbps
ON
OFF
125 kbps
OFF
ON
250 kbps
OFF
OFF
500 kbps
ON
OFF
800 kbps
OFF
OFF
1000 kbps
ON
ON
Automated recognition
l
2
1
SSP94M1001
9400CAN003