Herunterladen Inhalt Inhalt Diese Seite drucken

Analog Output; Digital Inputs - Honeywell SHC Montageanleitung

Oem überhitzungsregler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

OEM SHC CONTROLLER – INSTALLATION INSTRUCTIONS
Temperature Impact
The temperature impact on AIN1 and AIN2 configured for
PT1000 temperature sensors is max. ±1 K with respect to a
reference temperature of 25 °C.
The temperature impact on AIN1 and AIN2 configured for
NTC10K or NTC20K temperature sensors is max. ±0.2 K with
respect to a reference temperature of 25 °C.
Universal Inputs (AIN3, AIN4)
The SHC Controller has two universal inputs (AIN3, AIN4 =
terminals 24-27) which can be configured for PT1000,
NTC10K, or NTC20K temperature sensors or voltage input
(0.5...4.5 V / 0...10 V).
Accuracy (without sensor)
The accuracy of AIN3 and AIN4 configured for PT 1000 is
max: ±0.5 K in the range of
-70...+120 °C.
The accuracy of AIN3 and AIN4 configured for NTC10K,
NTC20K is max: ±0.5 K in the range of -25...+120C.
The accuracy of AIN3 and AIN4 configured for voltage input is
max. ±1%.
Input Resistance
The input resistance of AIN3 and AIN4 configured for voltage
input is min. 20 kOhm.
Temperature Impact
The temperature impact on AIN3 and AIN4 configured for
PT1000 sensors is max. ±1.5 K with respect to reference
temperature 25°C.
The temperature impact on AIN3 and AIN4 configured for
NTC10K, NTC20K is max. ±0.2 K with respect to a reference
temperature of 25°C.
The temperature impact on AIN3 and AIN4 configured for
voltage signals is max. ±1% with respect to a reference
temperature of 25 °C.
Voltage/Current Inputs (AIN5, AIN6)
The SHC Controller has two voltage/current inputs (AIN5,
AIN6 = terminals 28-32) which can be configured for voltage
(0.5...4.5 V / 0...10 V) or current (4...20 mA) input.
Accuracy (without sensor)
The accuracy of AIN5 and AIN6 configured for voltage input is
max. ±1%.
The accuracy of AIN5 and AIN6 configured for current input is
max. ±2.5%.
Input Resistance
The input resistance of AIN5 and AIN6 configured for voltage
input is min. 20 kOhm.
MU1B-0441GE51 R0710B
The input resistance of AIN5 and AIN6 configured for current
input is max. 250 Ohm.
Temperature Impact
The temperature impact on AIN5 and AIN6 configured for
voltage input is max. ±1% with respect to a reference
temperature 25 °C.
The temperature impact on AIN5 and AIN6 configured for
current input is max. ±1% with respect to a reference
temperature of 25 °C.

Analog Output

The SHC Controller provides one voltage output ( terminals
33-35) able to produce a voltage signal (0...10 V).
Max. Current Draw
The max. current drawn from the voltage output is 1 mA.
Accuracy (10 kOhm load)
The accuracy of the voltage output (with a 10 kOhm load) is
max. ±25 mV.
Temperature Impact (10 kOhm load)
The temperature impact on the voltage output is max.
±100 mV with respect to a reference temperature of 25 °C.

Digital Inputs

The SHC Controller has three digital inputs (terminals 35-39),
capable of being configured to the following modes:
the ENABLER digital input,
the CLOSE digital input, and
the REVERSE OPERATION digital input.
ENABLER Digital Input
If the ENABLER digital input (terminals 38/39) changes from
active to inactive, the SAFE procedure is performed. Then the
valve remains in the attained position until the ENABLER
digital input becomes active again.
If the ENABLER digital input changes from inactive to active,
the power-up procedure is performed, followed by the start-up
procedure.
NOTE: For description of SAFE procedure and START up
procedure refer to Operating Instructions which can
be downloaded from webpage
cooling.com
CLOSE Digital Input
If the CLOSE digital input (terminals 37/38) changes from
inactive to active, the valve is driven to CLOSED position and
remains so until the CLOSE digital input becomes inactive
again.
8