GENERAL
The OEM SHC Controller comes complete with base plate,
main board, plug-in board, and a set of terminal blocks.
Fig. 1. OEM SHC Controller
There are two configurations to choose from, depending upon
your desired application:
Configuration for Brine-to-Water Heat Pumps: Control
algorithm for liquid/liquid refrigeration circuit is pre-
selected. Use of Honeywell temperature sensor type TS-
NFR and Honeywell pressure sensor type PSR is
required. Application-specific settings available, upon
request.
Configuration for Air-to-Water Heat Pumps: Control
algorithm for air/liquid refrigeration circuit is pre-selected.
Use of Honeywell temperature sensor type TS-NFR and
Honeywell pressure sensor type PSR is required.
Application-specific settings available, upon request.
BEFORE INSTALLATION
IMPORTANT
It is recommended that the SHC Controller be kept at
room temperature for at least 24 hours before applying
power; this is to allow the evaporation of any
condensation resulting from low shipping / storage
temperatures.
® U.S. Registered Trademark ▪ All Rights Reserved.
Copyright © 2010 Honeywell Inc.
SUPERHEAT CONTROLLER – OEM VERSION
CAUTION
The product may be mounted only by trained personnel who are
thoroughly familiar with all pertinent electrical safety rules.
To avoid electrical shock or equipment damage, you must turn
OFF the power supply before attaching / removing connections
to/from any terminals.
Do not power the SHC with line voltage!
If the product is mounted where unauthorized personnel has
access, the relays may not be used for switching line voltage
(230 Vac).
In case of relays switching line voltage, two neighboring relays
may switch the same phase, only.
Sensors and secondary (output) of transformer may not be
grounded simultaneously.
Grounding of secondary (output) of transformer is not
recommended.
Alarm relay without power must be recognized as "alarm" if used.
A 24 V emergency battery module (not included) can be
connected to the SHC to enable safe closing in the event of a
power failure. 1 Ah is recommended.
Sensors with current output 4...20 mA and ratiometric voltage
output 0.5 V...4.5 V may not be used simultaneously.
Connecting sensors by wires more than 6 m long may decrease
the accuracy of measured values.
To prevent damage to the compressor, the signal indicating
whether the compressor is running or not must be connected to
the SHC's enabler input in case the SHC is in the Automatic
Superheat Control mode while COLD STORE supervision is
disabled. If the SHC is operating in the Automatic Superheat
Control mode and COLD STORE supervision is simultaneously
enabled, the enabler input can be used (e.g., for main power
indication), but it may not be connected with compressor. If the
SHC is operating in any mode other than the Automatic
Superheat Control mode, the enabler input is ignored.
If supply voltage has been accidentally applied to the
voltage/current input, wait at least 15 minutes before switching
the SHC ON.
Disabling the Low superheat alarm and High superheat alarm is
not recommended.
Possible LOP alarm will be erased automatically when the SHC
enters the MANUAL, REMOTE, or CONFIGURATION mode.
A switch or circuit-breaker must be included in the installation; it
must be installed in close proximity to the controller and must be
marked as the disconnecting device for the controller.
If one of the supported Honeywell transformers (see section
"Accessories") is not used to supply the SHC controller, protect
the power input line G using an external 3A type T fuse.
Type SHC
INSTALLATION INSTRUCTIONS
MU1B-0441GE51 R0710B

Werbung

Inhaltsverzeichnis
loading

Inhaltszusammenfassung für Honeywell SHC

  • Seite 1 Alarm relay without power must be recognized as “alarm” if used.  A 24 V emergency battery module (not included) can be connected to the SHC to enable safe closing in the event of a power failure. 1 Ah is recommended. ...
  • Seite 2 181 x 110 x 40 mm (W x L x H). orientation desired. In the case of ceiling mounting, however, The OEM SHC Controller is suitable for mounting on both a it should not be operated at ambient temperatures exceeding standard rail (DIN EN 50022-35 x 7,5) and for installation in 45 °C.
  • Seite 3: Terminal Assignment

    OEM SHC CONTROLLER – INSTALLATION INSTRUCTIONS Terminal Assignment 154 mm The terminal blocks are arranged on two sides of the con- troller: the sensor side and the relay side. The terminals on round hole the controller consist of multiple sockets for screw terminal (diameter: 4 mm) plugs which come together with the controller.
  • Seite 4 LEDs The OEM SHC Controller features three LEDs: a green power LED (LED 1), a red alarm LED (LED 2), and a yellow status LED (LED 3). The various different possible blinking patterns and the corresponding meanings are listed in Table 2.
  • Seite 5: General Information

    The EEV is opening, closing, or synchronizing. A single blink (until the OFF position is single blink achieved; EEV in safety position; REV to close) also indicates that the SHC is powering up. 2 blinks REV valve is moving (i.e., the REV delay time is currently elapsing) 3 blinks Start ramp (incl.
  • Seite 6: Hardware Features

    The screw-type terminals support wiring with flexible or massive cables of 0.35 mm² up to 2.5 mm². Besides the Honeywell electronic expansion valve type EEV Two wires with a total thickness of 14 AWG can be twisted (models EV2, EV3, EV4), the controller provides presettings...
  • Seite 7 Table 5. Factory default settings of relay outputs relay output terminals relay mode default setting The SHC Controller has two temperature inputs (AIN1, AIN2 = terminals 21-23) which can be configured for PT1000, 15, 16 unused none NTC10K, and NTC20K temperature sensors.
  • Seite 8: Analog Output

    Universal Inputs (AIN3, AIN4) current input is max. ±1% with respect to a reference temperature of 25 °C. The SHC Controller has two universal inputs (AIN3, AIN4 = terminals 24-27) which can be configured for PT1000, Analog Output NTC10K, or NTC20K temperature sensors or voltage input (0.5...4.5 V / 0...10 V).
  • Seite 9: Application Info

    SUCTION LINE PRESSURE (pos. 17) TEMP. (pos. 6) The firmware of the SHC Controller supports sensors mounted in positions 1, 3, 6, 7, 9, 14, 17, and 20 defined in Table 8. NOTE: The max. permissible number of connected sensors at the same time is 6.
  • Seite 10: Sample Applications

    SHC-X9999 SHC OEM with customized configuration Contact Honeywell Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH...
  • Seite 11: Allgemein

    Regelalgorithmus für Luftverdampfer ist voreingestellt. Der der Regler-Aktivierungs-Eingang ignoriert. Einsatz von Honeywell Temperatur-Sensor Typ TS-NFR  Warten Sie mindestens 15 Min. vor dem Einschalten des SHC, falls und Honeywell Drucksensor Typ PSR ist vorgeschrieben. irrtümlich Versorgungsspannung an die Spannungs-/Stromeingänge Anwendungsspezifische Parametrierung ist auf Anfrage geschaltet wurde.
  • Seite 12: Klemmenbelegung

    (diameter: 4 mm) 181 x 110 x 40 mm (B x L x H). Der OEM SHC Regler kann auf Standardschiene (DIN EN 50022-35 x 7,5) montiert werden, im Schaltschrank oder an der Wand oder der Decke. Der Regler kann in horizontaler und in vertikaler Position betrieben werden.
  • Seite 13 ÜBERHITZUNGSREGLER OEM VERSION – MONTAGEANLEITUNG  Die Sensorseite (Klemmen 21-39) besteht aus Klemmen HINWEIS: Gemäß VDE Richtlinie ist eine Mischung von für sechs Analogeingänge, einen Analogausgang und drei Hoch- und Niederspannungssignalen an den Digitaleingänge. Relais nicht erlaubt.  Die Relaisseite (Klemmen 1-20) besteht aus Klemmen für die Spannungsversorgung (24 Vac/dc), den Steppermotor Ausgang, die RS485 Schnittstelle und die vier Relais.
  • Seite 14: Beschreibung

    Masse für Digitaleingänge 1 + 2 + 3 Leuchtdioden (LEDs) Der OEM SHC Regler verfügt über drei LEDs: Eine grüne Spannungsversorgungs-LED (LED 1), eine rote Alarm-LED (LED 2) und eine gelbe Status-LED (LED 3). Die verschiedenen Blinkmodi und die zugehörigen Bedeutungen sind in Tabelle 2 aufgelistet.
  • Seite 15: Spannungsversorgung

    ÜBERHITZUNGSREGLER OEM VERSION – MONTAGEANLEITUNG Tabelle 2. LED Blink-Kodierung Verhalten Bedeutung LED 1 (grüne Spannungsvers.- Versorgungsspannung liegt an. LED) Kein Alarm Batterieversorgung Zu niedrige Überhitzung LED 2 Zu hohe Überhitzung (rote Alarm-LED) Sensor Fehler LOP aktiv Konfigurationsfehler Kommunikationsfehler Fehler in Hardware Selbsttest Anlage ist ausgeschaltet (Sicherheitsposition) Einschaltphase oder EEV aktiv (öffnet/schließt) Umschaltrelais aktiv, Umschaltverzögerung läuft...
  • Seite 16: Schrittmotor-Ausgang

    1…1,000 Schritte HARDWARE FUNKTIONEN Neben den elektronischen Expansionsventilen Typ EEV von Honeywell (Modelle EV2, EV3, EV4) hat der Regler Vor- Schrittmotor-Ausgang einstellungen für die in Tabelle 3 gelisteten Schrittmotor- Der Regler kann bipolare Schrittmotoren mit 12 V oder mit 24 ventile mit den zugehörigen Parametern.
  • Seite 17 Temperatur Eingänge (AIN1, AIN2) Der Temperatureinfluß auf AIN1 und AIN2, konfiguriert für NTC10K oder NTC20K Temperatursensoren, ist max. ±0,2K Der SHC Regler hat zwei Temperatureingänge (AIN1, AIN2 = bezogen auf eine Referenztemperatur von 25 °C. Klemmen 21-23) die für PT1000, NTC10K und NTC20K Temperatursensoren konfiguriert werden können.
  • Seite 18: Universaleingänge (Ain3, Ain4)

    Universaleingänge (AIN3, AIN4) Der Temperatureinfluß auf AIN5 und AIN6, konfiguriert als Stromeingang, ist max. ±1% bezogen auf eine Referenz- Der SHC Regler hat zwei Universaleingänge (AIN3, AIN4 = temperatur von 25 °C. Klemmen 24-27), die für PT1000, NTC10K, oder NTC20K Temperatursensoren oder als Spannungseingänge...
  • Seite 19 SUCTION LINE PRESSURE (pos. 17) TEMP. (pos. 6) Die Gerätesoftware des SHC Reglers unterstützt Sensoren in den Positionen 1, 3, 6, 7, 9, 14, 17, und 20 gemäß Tabelle 8. HINWEIS: Die maximal erlaubte Anzahl gleichzeitig angeschlossener Sensoren ist 6.
  • Seite 20: Anwendungsbeispiele

    SHC-X9999 SHC OEM mit kundenspezifischer Konfiguration Kontaktieren Sie Honeywell Hergestellt für und im Auftrag des Geschäftsbereichs Environmental and Combustion Controls der Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Schweiz in Vertretung durch: Automation and Control Solutions Honeywell GmbH Hardhofweg...

Inhaltsverzeichnis