Special conditions are shown in the LC display if the Low Voltage Disconnect function
shuts off the load output or in case of various other error conditions. See section ERROR
DESCRIPTION for details.
Low Voltage Disconnect Function
The controller has 5 different modes to protect the battery from being deep discharged:
Mode 1: Disconnect at 22.8/45.6 V (at nominal load current) up to 23.8/47.6 V (at no load
current). Normal operation mode for good battery protection.
Mode 2: Disconnect at 22.0/44.0 V (at nominal load current) up to 23.5/47.0 V (at no load
current). Mode with lower disconnection point. Battery is cycled deeper, this can shorten
battery lifetime.
Mode 3: Disconnect at 22.0/44.0 V to 24.4/48.8 V depending on load current and previous
charging cycles. This adaptive mode leads to longer lifetime of the battery because it
allows recovery of the battery by full recharge. Maximum battery life.
Mode 4: Disconnect at 23.0/46.0 V fixed setting. Appropriate if bypass loads draw current
directly from battery.
Mode 5: Disconnect at 22.0/44.0 V fixed setting. Appropriate if bypass loads draw current
directly from battery. Mode with lower disconnection point. Battery is cycled deeper,
this can shorten battery lifetime.