5.2 Battery-module replacement

Safety recommendations

The battery can cause electrocution and high short-circuit currents. The following safety precautions
are required before servicing the battery components:
• remove watches, rings, bracelets and all other metal objects from the hands and arms,
• use tools with an insulated handle.
Battery tray removal on tower models
This operation must be performed when the UPS is switched OFF , and unplugged from AC source.
Mounting the new battery module
Carry out the above instructions in reverse order.
● To ensure safety and high performance, use only batteries supplied by EATON.
● Take care to firmly press together the two parts of the connector during remounting.
619-00470-02-i (en)
A
B
C
D

5. Maintenance

A - Remove the front panel.
B - Disconnect the battery block by
separating the two connectors
(never pull on the wires).
C - Remove the plastic protection cover
in front of the battery (one screw).
D - Pull the plastic tab to remove
the battery block and replace it.