Herunterladen Inhalt Inhalt Diese Seite drucken

Regulations; Transport; Assembly; Installation Location - Buderus PW 500.6-C Installations- Und Wartungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
3

Regulations

Observe the following directives and standards:
• Local regulations
• EnEG (in Germany)
• EnEV (in Germany)
Installation of, and equipment for, heating and water heating systems:
• DIN and EN standards
– DIN 4753, part 1: DHW cylinders and DHW heating systems for
potable and heating water; requirements, identification,
equipment and testing
– DIN 4753, part 5: Thermal insulation of DHW cylinders up to
1000 l nominal capacity – requirements and testing (product
standard)
– DIN EN 12828: Heating systems in buildings - Design for DHW
heating systems
– DIN EN 12897: Water supply – regulation for cylinder DHW
heaters (product standard)
1)
– DIN 18380: VOB
; heating systems and central water heating
systems
1)
– DIN 18381: VOB
; gas, water, and waste water installation work
within buildings
– VDE regulations
4

Transport

DANGER: Risk to life through falling load.
▶ Only use lifting cables that are in a faultless condition.
▶ Only insert hooks into the lifting eyes provided.
Tilting danger with forklift trucks or pallet trucks.
WARNING: Risk of injury through carrying heavy loads
and inadequately securing loads for transport!
▶ At least two persons are required for transportation
and installation.
▶ Use suitable means of transport.
▶ Secure the buffer cylinder to prevent it falling.
A crane is appropriate for transport. Alternatively the cylinder can be
transported using a pallet truck or forklift truck ( Fig. 4, page 68).
Applies to 750...1300 litre cylinders:
▶ Remove the foil jacket and rigid foam shells before
transporting and store in a clean place.
1) VOB: German contract construction procedures – Part C: General technical
specifications in construction contracts (ATV)
PW/P/PR/PNR/PNRZ... – 6 720 817 509 (2017/05)
5

assembly

▶ Check that the buffer cylinder is complete and undamaged.
5.1

Installation location

NOTICE: Risk of material damage from frost and corrosion.
▶ Site the buffer cylinder in a dry, frost-free room.
If there is a danger that water may collect on the floor of the installation
site:
▶ Position the buffer cylinder on a plinth.
▶ Site the buffer cylinder in dry, ventilated internal areas that are free
from the risk of frost.
▶ Observe the minimum room height ( table 6, page 66, table 7,
page 67 and table 8, page 68) and minimum wall clearances
( fig. 5, page 69) in the installation location.
5.2

Installing the temperature sensor

500 litre cylinder ( Fig. 6ff, page 69)
Assembly is also possible once the insulation has been installed.
▶ Observe the technical guide when positioning the sensor.
▶ Apply heat conducting paste to the contact surfaces.
▶ Insert the temperature sensor with installation set (part of the sensor
set) in the sensor pocket until it comes to a stop.
▶ Mark the temperature sensor leads at the end of each lead according
to sensor use.
▶ Route the sensor lead to the controller, ensuring it will be possible to
install the insulation.
▶ Electrical connection to the sensor leads. Observe the controller
installation instructions during this process.
750...1300 litre cylinder ( Fig. 7, page 70)
▶ Observe the technical guide when positioning the sensor.
▶ Apply heat conducting paste to the contact surfaces.
▶ Insert the temperature sensor into the spring clip so that the entire
length of the sensor surface makes contact with the storage cylinder.
▶ Mark the temperature sensor leads at the end of each lead according
to sensor use.
▶ Route the sensor lead to the controller, ensuring it will be possible to
install the insulation.
▶ Electrical connection to the sensor leads. Observe the controller
installation instructions during this process.
Regulations
3
39

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis