Herunterladen Inhalt Inhalt Diese Seite drucken

Bus Installation; Ex Data; Figure 1-5 Bus Installation - Honeywell STT17F Bedienungsanleitung

Foundation fieldbus messumformer fuer stt3000 smart temperature transmitter
Inhaltsverzeichnis

Werbung

English

1.7 Bus Installation

Segment coupler
Power supply
Safe area
Segment coupler, Ex
Power supply, Ex
To additional
segment couplers

Figure 1-5 Bus Installation

6
STT17F Smart Temperature Transmitter Operator Manual
STT17F-BN
2
1
F
max. 16
OUNDATION
Bus
termination
Hazardous area
STT17F-BS
2
1
F
max. 10
OUNDATION
Bus
termination
2/06

1.8 Ex Data

EEx / I.S. approval STT17F-BN:
KEMA 06ATEX0045 X .....................
Ex / I.S. data:
Signal output / supply, terminal 1 to 2:
STT17F-BN
Zone 2, EEx nA [nL] IIC
Division 2,
nonincendive
No
Unit
barrier
U i
32 VDC
T1...T4
T
< 85°C
amb.
T5
T
< 75°C
amb.
T6
T
< 60°C
amb.
Sensor input, terminal 3, 4, 5 and 6:
U
................................................... : 5.7 VDC
o
I
.................................................... : 8.4 mA
o
P
.................................................... : 12 mW
o
L
.................................................... : 200 mH
o
C
................................................... : 40 µF
o
EEx / I.S. approval STT17F-BS:
KEMA 06ATEX0046 X .....................
Applicable in zone .......................... 0, 1, 2, 20, 21 or 22
2/06
STT17F Smart Temperature Transmitter Operator Manual
English
II 3 G
EEx nA [nL] II C T4...T6
II 1 GD or
II 2 (1) GD,
T65°C...T105°C
EEx ia IIC or
EEx ib [ia] IIC T4...T6
7