(peak period). The temperature can be selected using the up/down arrow
keys. The minimum temperature is 37°C in Kinder garden and 41°C in apart-
ments and the maximum temperature is the selected maintain temperature.

3.1.9 Pre-Programs

The HWAT-ECO has 7 default timer programs. See 5.5.2 Diagrams,
page 34 for more information. A pre-program can be selected using the up/
down arrow keys. Press Enter to confirm your choice. HWAT-ECO takes a
few seconds to copy the default program to the internal memory. During
this time a row of dots will show in the display.
Fig. 5
Program name
Constant
Apartments
Prison
Hospital / Nursing Home I - 3
Hotel
Sport Centre
Office

3.1.10 Trace boiler

The trace boiler setting is included to ensure that the heating cable tem-
perature does not exceed the boiler temperature. The boiler temperature is
measured with the external temperature sensor. The HWAT-ECO memorizes
the highest measured temperature over the last 24 hours. With the up/down
arrow keys the setting can be altered between OFF and ON with a tempera-
ture difference from 5°C between boiler temperature and maintain tempera-
ture. Press Enter to confirm your choice. If the boiler temperature is too low
the maximum temperature is lowered to the boiler temperature minus the
trace temperature. In this case the green trace boiler LED will be on.
3.1.11 Sound alarm
Inside the unit a smal buzzer sounds during an error condition.
With this setting you can switch the sound into different modes: continuous,
10 minutes, 1 minute, 10 seconds or off.
Finishing "Quick install"
Press Enter to start the unit.
With ESC it is possible to retrace all menu items to check the settings.
After starting the unit the display shows date, time, temperature setting
and a * to indicate that the unit is unlocked.
Diagram number Building type
I - 0
I - 1
I - 2
I - 4
I - 5
I - 6
Constant temperature
Apartment block
Prison
Hospital / Nursing Home
Hotel
Sport centre / Swimming pool
Office