Herunterladen Inhalt Inhalt Diese Seite drucken

Enocean Equipment Profiles Eep A5-10-0C Temperature Sensor And Occupancy Control; Enocean Equipment Profiles Eep A5-10-05 Temperature Sensor, Set Point And Occupancy Control - Kieback&Peter Tc23 Produktbeschreibung

Inhaltsverzeichnis
Datenblatt 1.15-10.023-01-DE
TC23, TCF23

EnOcean Equipment Profiles EEP A5-10-0C Temperature Sensor and Occupancy Control

- TC23
RORG
A5
4BS Telegram
FUNC
10
Room Operating Panel
TYPE
0C
Temperature Sensor and Occupancy Control
Offset Size Bitange
0
16
DB3.7...DB2.0 Not Used (= 0)
16
8
DB1.7...DB1.0 TemperatureTMP
24
4
DB0.7...DB0.4 Not Used (= 0)
28
1
DB0.3
29
2
DB0.2...DB0.1 Not Used (= 0)
31
1
DB0.0
EnOcean Equipment Profiles EEP A5-10-05 Temperature Sensor,
Set Point and Occupancy Control
- TCF23
RORG
A5
4BS Telegram
FUNC
10
Room Operating Panel
TYPE
05
Temperature Sensor, Set Point and Occupancy Control
Offset Size Bitange
0
8
DB3.7...DB3.0 Not Used (= 0)
8
8
DB2.7...DB2.0 Set point
16
8
DB1.7...DB1.0 Temperature
24
4
DB0.7...DB0.4 Not Used (= 0)
28
1
DB0.3
29
2
DB0.2...DB0.1 Not Used (= 0)
31
1
DB0.0
A
Data
ShortCut Desription
LRN Bit
LRNB
Occupancy
OCC
Data
ShortCut Desription
SP
TMP
LRN Bit
LRNB
Occupancy
OCC
Valid Range
Temperature
255...0
(linear)
LRN Bit
Enum:
0: Teach-in telegram
1: Data telegram
Occupancy button Enum:
1: Button released
0: Button pressed
Valid Range
Set point (linear)
0...255
Min.- ... Max+
Temperature
255...0
(linear)
LRN Bit
Enum:
0: Teach-in telegram
1: Data telegram
Occupancy button Enum:
1: Button released
0: Button pressed
Ausgabe 2014-04-17
Produktbeschreibung
Scale
Unit
0...+40
°C
Scale
Unit
0...255
N/A
0...+40
°C