Herunterladen Inhalt Inhalt Diese Seite drucken

Floor Drying Parameters - Inocal PROMATIC CMP25-2 Bedienungsanleitung

Witterungsgeführte heizungsregler des mischerheizkreises
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Settings for heat sources
Para-
Function
meter
MAXIMUM BOILER TEMPERATU-
S3.1
RE
BOILER TEMPERATURE INCRE-
S3.2
ASE FOR MIXING CIRCUIT

FLOOR DRYING PARAMETERS

In group F1 are parameters for floor drying:
The procedure for setting floor drying parameters is the same as for the
service settings (see page 32).
Floor drying parameters
Para-
meter
F1.1
ACTIVATION OF FLOOR DRYING
F1.2
INTERVAL 1: DURATION
F1.3
INTERVAL 1: START TEMPERATURE
F1.4
INTERVAL 1: END TEMPERATURE
F1.5
INTERVAL 2: DURATION
F1.6
INTERVAL 2: START TEMPERATURE
F1.7
INTERVAL 2: END TEMPERATURE
F1.8
INTERVAL 3: DURATION
F1.9
INTERVAL 3: START TEMPERATURE
F1.10
INTERVAL 3: END TEMPERATURE
F1.11
INTERVAL 4: DURATION
F1.12
INTERVAL 4: START TEMPERATURE
F1.13
INTERVAL 4: END TEMPERATURE
:
Parameter description
Setting of maximal boiler temperature.
Setting of difference between boiler temperature and
calculated stand-pipe temperature.
:
Function
35
Setting
Default value
range
60 ÷ 160 °C
90
0 ÷ 25 K
5
Setting
Default
range
value
0- NO
0
1- YES
1 ÷ 15 days
10
10 ÷ 60 °C
20
10 ÷ 60 °C
20
1 ÷ 15 days
5
10 ÷ 60 °C
20
10 ÷ 60 °C
50
1 ÷ 15 days
10
50
10 ÷ 60 °C
10 ÷ 60 °C
50
1 ÷ 15 days
5
10 ÷ 60 °C
50
10 ÷ 60 °C
20
Service settings manual

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis