Settings for heating circuit
Parameter
Function
P2.2
PARALLEL SHIFT OF
HEATING CURVE
P2.3
DURATION OF BOOST
HEATING
P2.4
ROOM TEMPERATURE
INCREASE BY BOOST
HEATING
P2.5
PRIORITY OF D. H. W.
WARMING
Settings for heat source
Parameter
Function
P3.1
MINIMUM BOILER
TEMPERATURE

HEAT CURVE

Heating curve steepness tells us, what temperature is required for the heating bodies by
a determined outdoor temperature. The steepness setting depends on the type of heating
system (floor, wall, radiator, convector heating) and insulation of the building.
Adjusting the heating curve steepness
If you have enough data, you can determine the heating curve steepness with a calcula-
tion, otherwise from experience, based from the evaluation of heating system dimension-
ing and building insulation.
The steepness is set correct, if the room temperature remains stable, even by large out-
door temperature changes.
Until the outdoor temperature remains above + 5 °C, you can adjust the room tempera-
ture with changing day or night temperature or with parallel shift of the heating curve.
If it gets colder in the building, while the outdoor temperature is dropping, then the heat
curve steepness is set too low - you should increase the setting.
If the object by low outdoor temperatures gets warmer, the heat curve steepness needs
to be decreased.
The maximum steepness increase/decrease should not be greater than 0,1 to 0,2 units at
one observation. At least 24 hours must expire between two observations.
Service settings manual
:
Parameter description
Parallel shift of heating curve (calculated stand pipe
temperature).
Use this setting to eliminate deviation between actual and
set-point room temperature.
Duration of boosted room temperature by changeover
from night to day heating period.
Setting of boost temperature by changeover from night to
day heating period.
Setting if d. h. w. warming has priority to room heating.
:
Parameter description
Setting of minimal boiler temperature.
30
Default
Setting range
value
-15 ÷ 15 K
0
0 ÷ 200 min
0
0 ÷ 8 K
4
0- NO
0
1- YES
Default
Setting range
value
10 ÷ 90 °C
40