Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
AVENTICS | EV03 | R414008223–BAL–001–AA | English
Events
Table 12:
Events
Event
Definition
Type
codes
0x5111
Primary supply
Warning
voltage under-run
0x6320
Parameter error
Error
Parameter
Communication errors due to timeout!
Communication errors (timeout) can arise if the IO-Link master executes
a "parameter save".
O Make sure that the IO-Link master does not execute a parameter save while
you make entries.
Parameters are included in the contents of the configuration file.
The parameters sent to the device via the IO-Link will overwrite the existing
parameters on the device!
No parameter handler is used in this process.
Table 13:
Parameter
Index
Bit length
Name
2000
8 bits
Beginning of pressure range
2001
8 bits
Final pressure range value
2002
8 bits
Minimum set point
2003
2 bits
Control dynamics
2004
2 bits
Control accuracy
10 Commissioning the EV03 Pressure
Regulator
Before commissioning the EV03 pressure regulator, you must first assemble it and
connect it to your system.
Danger due to loose screws or connections!
Danger of injury!
O Check all screws and connections before starting the system.
Danger of burns caused by hot surfaces!
Touching the surfaces of the EV03 during operation could cause burns.
The temperature on uncoated metal can exceed 64 °C and on polymers can
exceed 85 °C.
O Let the device cool off before working on it.
O Do not touch the device during operation.
Shortened product service life if operated without operating pressure!
Operation with the supply voltage and set point applied, but no operating
pressure, can result in a shortened product service life.
O Never operate the device without compressed air.
Commissioning may only be carried out by qualified electrical or pneumatic
personnel or an instructed person under the direction and supervision
of qualified personnel (see "Personnel qualifications").
Comment
Undervoltage (UA < 19.2 V),
IO-Link allows for lower voltages but
the device does not work as intended
below this threshold.
Parameters were transferred
incorrectly or incorrect parameters
were transferred and not accepted
NOTICE
Value range
0 to 50%
20 to 100%
1 to 100%
Speed opt./
plug&play/
value opt.
Optimized/
plug&play/
generous
CAUTION
NOTICE
O Always observe the system documentation when commissioning the relevant
system component.
1. Make sure that the system is not under pressure.
2. Check all screws and connections once more before starting the system.
3. Switch on the power supply.
4. Check the LED displays on all modules.
– The UL and UA LEDs must be green before switching on the operating
pressure.
– The DIAG LED must be off before commissioning.
If the LEDs are in the correct state:
5. Switch on the compressed air supply.
Make sure that the operating pressure lies at least 1 bar above the maximum
output pressure to be controlled. Otherwise, only a reduced output pressure
range is available.
11 Disposal
O Comply with national regulations regarding disposal.

12 Troubleshooting

Table 14 contains an overview of malfunctions, possible causes, and remedies.
If you cannot remedy a malfunction, please contact AVENTICS GmbH.
The address is printed on the back cover of these instructions.
Table 14:
Table of malfunctions
Malfunction
Possible cause
No output pressure
No power supply
present
No set point stipulated
No operating pressure
Output pressure too low
Operating pressure too low
(less than the set point)
A consumer with a high air
consumption is located in
the EV03 operating line and
results in a large pressure
drop in the device.
Operating pressure less
than 1 bar above the
maximum output pressure
to be controlled.
Air is audibly escaping
Seal is missing or damaged Check the seals and
Pressure regulator is not
leaktight
Pressure regulator
Device with current input is
emits short pressure
operated with voltage set
pulses
point
Outlet pressure jumps
Set point too high
to the level of the
(> 20 mA or > 10 V)
operating pressure.
Output pressure too
Dynamic pressure in
high
exhaust
DIAG LED illuminated
Parameter error
red
Safety cut-off active
21
Remedy
Connect the power
supply.
Check the polarity
of the power supply.
Switch on system
component.
Stipulate a set point.
Connect the operating
pressure.
Increase the operating
pressure
Reduce air consumption.
Adjust the operating
pressure to at least 1 bar
above the maximum
output pressure to be
controlled.
replace, if necessary.
Exchange the pressure
regulator.
Stipulate the correct type
of set point.
Stipulate the correct set
point.
Check the exhaust line.
Stipulate valid
parameterization.
Exchange device since
a pressure sensor is
defective.

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis