Herunterladen Diese Seite drucken

Siemens SIMATIC S7 CPU 417-4 H Produktinformation Seite 23

Firmware-stand v 2.1.5
Vorschau ausblenden Andere Handbücher für SIMATIC S7 CPU 417-4 H:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

S
Change and load the user program (see Section 10.3.2 for PCS7 or Section10.5.2 for
STEP7)
S
Stop the standby CPU (see Section 10.3.3 for PCS7 or Section 10.5.3 for STEP7)
S
Download the new hardware configuration to the standby CPU (see Section 10.3.4 for
PCS7 or Section 10.5.4 for STEP7)
S
Switch off the power supply to the standby subsystem
S
Remove the IM460 and the external DP master interface
S
Switch on the power supply to the standby subsystem again
S
Switch to the CPU with a modified configuration (see Section 10.3.5 for PCS7 or Section
10.5.5 for STEP7)
S
Transition to redundant system mode (see Section 10.3.6 for PCS7 or 10.5.6 for STEP7)
S
STEP7 only: Change and load organization blocks (see Section 10.5.8)
Removing Interface Modules in Case of the Master and Standby Subsystems
S
Change the hardware configuration offline (see Section 10.3.1 for PCS7 or Section 10.5.1
for STEP7)
S
Change and load the user program (see Section 10.3.2 for PCS7 or Section10.5.2 for
STEP7)
S
Stop the standby CPU (see Section 10.3.3 for PCS7 or Section 10.5.3 for STEP7)
S
Download the new hardware configuration to the standby CPU (see Section 10.3.4 for
PCS7 or Section 10.5.4 for STEP7)
S
Switch off the power supply to the standby subsystem
S
Remove the external DP master interface
S
Switch on the power supply to the standby subsystem again
S
Switch to the CPU with a modified configuration (see Section 10.3.5 for PCS7 or
Section 10.5.5 for STEP7)
S
Switch off the power supply to the standby subsystem
S
Remove the external DP master interface
S
Switch on the power supply to the standby subsystem again
A5E00130864-03
CPU 417-4H
23

Werbung

loading