Limitation and cascade functions:
- Maximum and minimum values
- Proportional band and integration time
Winter / Summer change-over function, set-
points
Compensation function, curve points
5.
Select PS4 level to finalize application set-
tings, displays depending on application se-
lected:
Y1 and Y2 settings:
- Proportional band and integration time
- Minimum and maximum value control
signal
Comfort and Economy setpoints for heating
and cooling
4/8
26.08.2009
6.
Quit the commissioning menu with EXIT PS
display by pressing the SEL button (
The application starts, all sensors will be
checked and existing sensors will be high-
lighted for future fault status messages.
Normal mode display appears with the main
sensor value (X1) and the modulating output
values (Y1 and Y2):
Notes:
 The commissioning level can be changed by
pressing the navigation buttons (
simultaneously for 5 sec.
 Information displays are always available from
normal mode, by pressing one of navigation
buttons (
):
- Comfort setpoint (SP-...
- Economy setpoint (SP-... )
- Temperature sensor values
- Modulating output values (Y1 and Y2)
- Actual application type
CE1G3342de,en
).
)
)